2.  Configure the MMIGRS2 

display with MCX, EKE or 

AK-PC

After turning on and connecting the display, follow these steps:

Press and hold the X and • of the MCX keyboard 

until it enters the BIOS:

Go to the CAN sub-menu and enter "ACTIVE 

NODES":

If you see an “L” and the number “1” in the diagram, the display is online with the controller.

This diagram shows that the address display 

126

 is online with the controller address 

1

.

This menu shows that the display found a device on the network.

The equipment address that the display found is corresponding to the location where the number 1 

appears. In image A, the equipment found is with address 1. In image B, it has address 10.

The equipment address (MCX, EKE or AK-PC can be changed).

When the previous steps are OK and the display 

recognizes the controller, go to the home menu 

and find the option "MCX SELECTION":

Select "MAN SELECTION" and enter the address 

of the equipment to which the display is 

connected (network address).

Image A

Image B