Tests

 

 

Tests  

The MCD3000 soft starter operation can be verified 
using various dynamic test procedures. There is also a 
static test procedure that will give accurate information 
on the condition of the soft starter. The following 
information details the test procedures, test equipment 
required and actions to be taken from the test results. 
 

Start Performance Test 

This is a dynamic test that verifies the correct 
operation of the MCD3000 soft starter during “start 
mode”. You will need a suitably rated ammeter. Best 
results are achieved using a clip on analogue 
ammeter. Use the following procedure: 
1.  Determine the expected start current by 

multiplying the programmed Motor Full Load 
Current (Parameter 1) by the Current Limit 
(Parameter 2). 

2.  Start the motor and measure the actual start 

current. 

3.  If the expected start current and the measured 

start current are the same, the soft starter is 
performing correctly. 

4.  If there is a large variation between the expected 

start current and the measured start current, this 
could indicate a faulty MCD3000 Main Control 
Module or internal Current Transformer. Exchange 
the Main Control Module. If the fault remains 
check the Current Transformers by measuring the 
secondary resistance for continuity and visually 
inspecting these circuits. 

5.  If Current Ramp start mode is used, the minimum 

expected start current is the programmed Motor 
Full Load Current (Parameter 1) multiplied by the 
Initial Current (Parameter 3). Continue with Steps 
2 to 4 detailed above. 

 

Run Performance Test 

This is a dynamic test that verifies the correct 
operation of the MCD3000 soft starter during “run 
mode”. You will need a suitably rated voltmeter. Use 
the following procedure: 
1.  Ensure that the soft starter is in “run mode”. This 

can be verified by making sure the “Run” LED 
located on the soft starter front display panel is 
illuminated. 

2.  Measure the voltage across each phase of the 

soft starter, ie.L1/T1, L2/T2, L3/T3. 

3.  The measured voltage should be less than 2VAC 

when the soft starter is operating correctly. If the 
voltage is significantly greater than 2VAC this 
could indicate: 

• 

A faulty firing circuit on the Main Control 
Module. Exchange the Main Control Module to 
see if the fault is removed. 

• 

A faulty SCR gate circuit. With a multimeter, 
measure the gate resistance (anode to cathode 
/ cathode to anode) of the suspect SCR. 
Comparative readings should be taken with a 
known healthy SCR device. If the test results 
are erroneous, replace the SCR. 

• 

A faulty firing loom circuit. Perform a continuity 
test on the firing loom circuit and visually 
inspect for a loose connection. 
 

Power Circuit Test 

This is a static test that verifies the condition of the 
MCD3000 soft starter SCRs, firing looms and Main 
Control Module. You will need a 500VDC insulation 
tester. A recommended model is the “Megger 
BM101/3” or similar. Do not use a hand generated 
insulation tester or a standard multimeter (analogue or 
digital). These will give erroneous test results. Use the 
following procedure: 
1.  Completely isolate the soft starter so that there 

are no main power connections to busbars L1, 
L2, L3 and T1, T2, T3. For safety, remove the 
control supply power to the soft starter terminals 
A1/A2 or A2/A3. 

2.  Using a suitable insulation tester measure the 

resistance across each phase of the soft starter, 
ie.L1/T1, L2/T2, L3/T3. These measurements 
should also be taken in the reverse direction, ie. 
T1/L1, T2/L2, T3/L3. 

3.  A resistance measurement of 33 to 40k

 across 

each phase indicates a healthy condition. All 
readings should be similar. 

4.  A resistance of less than 10k

 would indicate that 

the SCR power device is suffering from excessive 
leakage or a complete short circuit. Replace the 
faulty SCR and analyse the system for common 
causes of SCR failure (Refer to Section 5.1, 
Typical Causes of SCR Damage). 

 

NB! 

Damage to an SCR does not necessitate 
mandatory replacement of the MCD3000 Main 

Control module. Replace of the Main Control module 
should be considered only after first having replaced 
the damaged SCR(s) and tested the MCD3000 for 
correct operation. 
 
5.  A resistance of greater than 60k

 could indicate a 

faulty Main Control Module or firing loom. 
Exchange the Main Control Module to see if the 
fault is removed. If the fault remains, check the 
firing loom for continuity and inspect all 
connections. 

Содержание MCD3000 Series

Страница 1: ...15 2 4 Control Input Test 16 2 5 Power Transformer Test 16 Section 3 0 Component Replacement Procedures 3 1 Main Control Module 3007 3132 17 3185 3800 17 3 2 Identity Module 3007 3132 18 3185 3800 18...

Страница 2: ...anfoss trademark Contents 4 8 3030 3055 T7 46 4 9 3075 3110 T7 47 4 10 3132 T7 48 4 11 3185 3500 T7 49 4 12 3600 3800 T7 50 Section 5 0 Appendix 5 1 Typical Causes of SCR Damage 51 5 2 Output Relay Co...

Страница 3: ...nection ceases Symbols used in this manual When reading this manualyou will come across different symbols that require special attention The symbols used are the following Indicates something to be no...

Страница 4: ...448 00 1 1 1 1 1 1 1 1 175G5089 0DCC2 991 00453 00 1 1 1 1 1 1 1 1 1 1 1 1 1 175G5088 0DCC1 991 00448 00 175G5089 0DCC2 991 00453 00 Identifying Main Control Modules Thetwo Main Control Module types c...

Страница 5: ...447 00 1 175G5093 0DCT022 990 00677 00 1 175G5094 0DCT030 990 00449 00 1 175G5095 0DCT037 990 00682 00 1 175G5096 0DCT045 990 00455 00 1 175G5097 0DCT055 990 00456 00 1 175G5098 0DCT075 990 00697 00 1...

Страница 6: ...MCD3037 MCD3045 MCD3055 MCD3075 MCD3090 MCD3110 MCD3132 MCD3185 MCD3220 MCD3300 MCD3315 MCD3400 MCD3500 MCD3600 MCD3700 MCD3800 number per unit 175G3052 990 02002 00 1 175G3053 990 02003 00 1 175G305...

Страница 7: ...0 MCD3300 MCD3315 MCD3400 MCD3500 MCD3600 MCD3700 MCD3800 T5 200 525V T7 200 690V number per unit Not required 175G5115 0DSB1H 990 00451 00 1 1 1 1 1 1 1 1 175G5112 0DSB2 990 00695 00 175G5116 0DSB2H...

Страница 8: ...MCD3000 Series 8 MG 15 B2 02 VLT is a registered Danfoss trademark Spare Parts 175G5113 0DSB4 990 00739 00 175G5117 0DSB4H 990 00740 00 175G5114 0DSB5 990 00895 00 175G5118 0DSB5H 990 00896 00...

Страница 9: ...5G5121 SKKT72 16 3 175G5122 SKKT92 16 3 3 175G5123 SKKT122 16 3 175G5124 SKKT132 16 3 175G5125 TT162N16 3 3 175G5126 TT250N16 3 175G5127 TT330N16 3 3 Power Assemblies number per unit 175G5128 8DAT185...

Страница 10: ...MCD3000 Series 10 MG 15 B2 02 VLT is a registered Danfoss trademark Spare Parts 175G5123 SKKT122 16 175G5124 SKKT132 16 175G5125 TT162N16 175G5126 TT250N16 175G5127 TT330N16...

Страница 11: ...arts 175G5128 8DAT185 994 00715 00 175G5129 8DAT220 994 00717 00 175G5130 8DAT300 994 00719 00 175G5131 8DAT315 994 00721 00 175G5132 8DAT400 994 00723 00 175G5133 8DAT500 994 00725 00 175G5134 8DAT60...

Страница 12: ...Part Number MCD3007 MCD3015 MCD3018 MCD3022 MCD3030 MCD3037 MCD3045 MCD3055 MCD3075 MCD3090 MCD3110 MCD3132 MCD3185 MCD3220 MCD3300 MCD3315 MCD3400 MCD3500 MCD3600 MCD3700 MCD3800 number per unit 175G...

Страница 13: ...D3132 MCD3185 MCD3220 MCD3300 MCD3315 MCD3400 MCD3500 MCD3600 MCD3700 MCD3800 CV4 230V 400V CV2 110V 230V number per unit 175G5139 1PT10AV 175G5150 1PT10DV 1 1 1 1 175G5140 1PT17AT 175G5151 1PT17DT 1...

Страница 14: ...MCD3000 Series 14 MG 15 B2 02 VLT is a registered Danfoss trademark Spare Parts 175G5141 1PT23AT 175G5152 1PT23DT 175G5142 1PT40AT 175G5153 1PT40DT 175G5143 1PT55AT 175G5154 1PT55DT...

Страница 15: ...perating correctly If the voltage is significantly greater than 2VAC this could indicate A faulty firing circuit on the Main Control Module Exchange the Main Control Module to see if the fault is remo...

Страница 16: ...connected to a plastic connector block that the Main Control Module is seated into 2 Remove the Main Control Module from the soft starter 3 At the plastic connector block measure the voltage between...

Страница 17: ...terminal cover Step 2 Undo fixing screws 4 and lift off Control Module NB Lift the control module straight off DO NOT Pivot Step 3 Fit new Control Module in reverse order Control Module MCD3185 MCD38...

Страница 18: ...ted Step 4 Detach the Identity Module from the top gland plate for models MCD3075 3132 the fan grill below the top gland plate must be removed to allow detachment Fit the new Identity Module in revers...

Страница 19: ...ction Module Step 4 Fit the new Snubber Overvoltage Protection Module in reverse order Snubber Overvoltage Protection Module MCD3075 MCD3132 Step 1 Disassemble the MCD3000 as described for Identity Mo...

Страница 20: ...Identity Module All plugs have locating mechanisms to ensure they are correctly fitted The three temperature detector plugs are interchange and can be connected to any of the temperature detector pin...

Страница 21: ...s trademark 21 Component Replacement Procedures Step 7 Unplug the SCR leads Step 8 Undo fixing screws 2 undo the fixing nuts 6 and remove the Snubber Overvoltage Protection Module Step 9 Fit the new S...

Страница 22: ...Undo fixing screws 4 and lift off Control Module Step 3 Unplug the three temperature detector plugs and the CT plug from the identity module All plugs have locating mechanisms to ensure they are corr...

Страница 23: ...p 9 Fit the new Snubber Overvoltage Protection Module in reverse order SCRs MCD3007 MCD3132 Step 1 Remove the Main Control Module Identity Module using the method described on page 18 Step 2 Unplug th...

Страница 24: ...the screw 1 connecting the output bus bar T1 T2 or T3 to the top of the SCR being replaced Model Torque MCD3007 MCD3030 4 NM MCD3037 MCD3075 7 NM MCD3090 MCD3132 12NM Step 6 Slide the busbar up or do...

Страница 25: ...Module All plugs have locating mechanisms to ensure they are correctly fitted The three temperature detector plugs are interchange and can be connected to any of the temperature detector pins on the I...

Страница 26: ...he same mechanical orientation as the original Power Assembly Step 10 Undo the bolts 24 securing the bus bars to the power assemblies These bolts are tightened to 12NM for models MCD3185 3500 and 17NM...

Страница 27: ...per SCR connected to each of the SCRs Firing Loom Connection Detail MCD3007 3030 MCD3037 3045 MCD3055 Step 4 Undo and remove the screws 2 per SCR connecting the input and bypass bus bars L1 B1 L2 L3 B...

Страница 28: ...on plate Step 10 Remove the screws 4 securing the fan bracket Step 11 Remove the fan bracket Step 12 Remove the fan from the fan bracket Step 13 Cut the plug from the end of the fan wiring loom leavin...

Страница 29: ...the MCD3000 Step 3 Undo the screws 2 securing the bus bar support bracket Step 4 Unclip the CT s and slide off the bus bar support bracket Note 1 For MCD3090 3110 this will also require the detachment...

Страница 30: ...t least 75mm wire between the cut and the plug Retain the plug protective sleeve and grommet so that these can be fitted to the new fan wiring during re assembly Crimp terminals are supplied with the...

Страница 31: ...g end caps fan grills from the left side of the MCD3000 Step 3 Undo the screws 2 securing the bus bar support bracket Step 4 Undo the scr ews securing the vertical support rail and slide the rail out...

Страница 32: ...the base plate Step 9 Remove the screws 6 securing the fan bracket This will also require the loosening of output bus bar T2 Step 10 Cut the crimp terminals 2 from the end of the fan wiring loom New c...

Страница 33: ...Power Assembly mounting screw 4 and remove the lower power assembly For models MCD3600 3800 is will also require removal of the polycarbonate fan insulation plate Step 3 Undo the Cooling Fan mountin...

Страница 34: ...plate from the MCD3000 Step 3 Undo the screws 2 securing the power transformer and earth wire Step 4 Cut the wiring MCD3007 3022 orange purple orange MCD3030 3055 orange purple orange white white run...

Страница 35: ...2 Remove the lower gland plate from the MCD3000 Step 3 Undo the screws 2 securing the power transformer and earth wire Step 4 Cut the wiring orange purple orange white white running from the PT Ensure...

Страница 36: ...plate from the MCD3000 Step 3 Undo the screws 2 securing the power transformer and earth wire Step 4 Unplug the white wires 2 running from the PT to the fan supply rectifier Step 5 Cut the wiring ora...

Страница 37: ...e screws 2 securing the power transformer and earth wire Step 3 Unplug the white wires 2 running from the PT to the fan supply rectifier Step 4 Cut the wiring orange purple orange running from the PT...

Страница 38: ...MCD3000 Series 38 MG 15 B2 02 VLT is a registered Danfoss trademark Component Replacement Procedures...

Страница 39: ...MCD3000 Series MG 15 B2 02 VLT is a registered Danfoss trademark 39 Schematics Schematics...

Страница 40: ...MCD3000 Series 40 MG 15 B2 02 VLT is a registered Danfoss trademark Schematics...

Страница 41: ...MCD3000 Series MG 15 B2 02 VLT is a registered Danfoss trademark 41 Schematics...

Страница 42: ...MCD3000 Series 42 MG 15 B2 02 VLT is a registered Danfoss trademark Schematics...

Страница 43: ...MCD3000 Series MG 15 B2 02 VLT is a registered Danfoss trademark 43 Schematics...

Страница 44: ...MCD3000 Series 44 MG 15 B2 02 VLT is a registered Danfoss trademark Schematics...

Страница 45: ...MCD3000 Series MG 15 B2 02 VLT is a registered Danfoss trademark 45 Schematics...

Страница 46: ...MCD3000 Series 46 MG 15 B2 02 VLT is a registered Danfoss trademark Schematics...

Страница 47: ...MCD3000 Series MG 15 B2 02 VLT is a registered Danfoss trademark 47 Schematics...

Страница 48: ...MCD3000 Series 48 MG 15 B2 02 VLT is a registered Danfoss trademark Schematics...

Страница 49: ...MCD3000 Series MG 15 B2 02 VLT is a registered Danfoss trademark 49 Schematics...

Страница 50: ...MCD3000 Series 50 MG 15 B2 02 VLT is a registered Danfoss trademark Schematics...

Страница 51: ...Over corrected bulk power factor correction on a lightly loaded system causing severe ringing voltages Overtemperature Blocked heatsinks or restricted ventilation Faulty cooling fans Inadequate venti...

Страница 52: ...itched directly Solution Before using an MCD3000 soft starter PCB mount output relay for direct switching of an electronic contactor coil consult the contactor manufacturer supplier to see if this is...

Страница 53: ...l contacts used for operating the remote control inputs must be low current low voltage types gold flash or similar These inputs are internally powered by 24VDC and must only be operated by external v...

Страница 54: ...MCD3000 Series 54 MG 15 B2 02 VLT is a registered Danfoss trademark Appendix...

Отзывы: