1.1.2 Ordering Code Numbers

Standard version code no: 130B1143

Coated version code no: 130B1243

1.2 Mounting Guidelines

1.2.1 Mounting of Option Modules in Slot B

The power to the frequency converter must be disconnected.

For A2, A3 and B3 enclosures:

Remove the  (Local Control Panel), the terminal cover, and the  frame from the frequency converter.

Fit the MCB10x option card into slot B.

Connect the control cables and relieve the cable by the enclosed cable strips.
Remove the knock out in the extended  frame delivered in the option set, so that the option will fit under the extended  frame.

Fit the extended  frame and terminal cover.

Fit the  or blind cover in the extended  frame.

Connect power to the frequency converter.

Set up the input/output functions in the corresponding parameters, as mentioned in this document.

For A5, B1, B2, B4, C1, C2, C3, C4, D, E and F enclosures:

Remove the  and the  cradle

Fit the MCB10x option card into slot B

Connect the control cables and relieve the cable by the enclosed cable strips

Fit the cradle

Fit  the 

MCB109 Instruction

1 Analog I/O Option MCB109

MI.38.B2.02 - VLT

®

 is a registered Danfoss trademark

5

  1

Содержание MCB109

Страница 1: ...nalog I O Option MCB109 3 Introduction 3 Ordering Code Numbers 5 Mounting Guidelines 5 Mounting of Option Modules in Slot B 5 Index 7 MCB109 Instruction Contents MI 38 B2 02 VLT is a registered Danfoss trademark 1 ...

Страница 2: ...1 Analog I O Option MCB109 MCB109 Instruction 2 MI 38 B2 02 VLT is a registered Danfoss trademark 1 ...

Страница 3: ... PID controllers with I Os for set point inputs transmitter sensor inputs and outputs for actuators Illustration 1 1 Principle diagram for Analog I O mounted in frequency converter Analog I O configuration 3 x Analog Inputs capable of handling following 0 10 VDC OR 0 20 mA voltage input 0 10V by mounting a 510Ω resistor across terminals see NB 4 20 mA voltage input 2 10V by mounting a 510Ω resisto...

Страница 4: ...span When analog inputs are used for temperature sensors it is possible to read out feedback value in both C and F When operating with temperature sensors maximum cable length to connect sensors is 80 m non screened non twisted wires Analog outputs terminal X42 7 12 Parameter group for read out and write 18 3 See also Programming Guide Parameter groups for set up 26 4 26 5 and 26 6 See also Progra...

Страница 5: ...move the knock out in the extended frame delivered in the option set so that the option will fit under the extended frame Fit the extended frame and terminal cover Fit the or blind cover in the extended frame Connect power to the frequency converter Set up the input output functions in the corresponding parameters as mentioned in this document For A5 B1 B2 B4 C1 C2 C3 C4 D E and F enclosures Remov...

Страница 6: ...A2 A3 and B3 enclosures A5 B1 B2 B4 C1 C2 C3 C4 D E and F enclosures 1 Analog I O Option MCB109 MCB109 Instruction 6 MI 38 B2 02 VLT is a registered Danfoss trademark 1 ...

Страница 7: ... 3 Building Management System 3 I I os For Set Point Inputs 3 M Mcb 109 0 Multi zone Control 3 N Ni1000 Temperature Sensor 3 O Outputs For Actuators 3 P Principle Diagram 3 Pt1000 Temperature Sensor 3 R Real time Clock rtc 4 T Transmitter sensor Inputs 3 MCB109 Instruction Index MI 38 B2 02 VLT is a registered Danfoss trademark 7 ...

Отзывы: