Safety functions: Safe Torque Off (STO) in accordance with EN IEC 61800-5-2
•
PROFIsafe version 2.4 communication
•
Two dual-channel digital inputs:
-
Safety function activation
-
Monitoring
-
Configurable reset behavior (automatic or manual reset).
•
LED status indication
•
Supply voltage
-
Internally supplied by the drive
-
24 V DC output for safety sensors available.
•
Safe output S37
1.5.3 Items Supplied
•
VLT® Safety Option MCB 152
•
VLT® Safety Option MCB 152 Installation Guide
1.5.4 Compatible Drive Series
The VLT® Safety Option MCB 152 is a standard B option compatible with:
•
VLT® AutomationDrive FC 302
•
VLT® Decentral Drive FCD 302
1.5.5 Front View
MCB 152
Safe Option
PROFIsafe
SW. ver. xx.xx
Option B
130B9860
LED:
1
1
2
3
4
5
6
7
8
9 10 11 12
2
3
4
Y33/
D
I1
A
G
N
D
G
N
D
G
N
D
G
N
D
D
I1
B
N
C
N
C
24
V
S
37
D
I2
A
D
I2
B
e3
0b
e1
00
.1
1
Illustration 2: VLT® Safety Option MCB 152 Front View
1.5.6 Hardware and Software Requirements
The following software versions are required as a minimum when using VLT® Safety Option MCB 152:
•
LCP software version 7.0
•
VLT® AutomationDrive FC 302 firmware version 7.26
•
VLT® Decentral Drive FCD 302 firmware version 8.23
•
PROFINET software version 3.0
•
VLT® Motion Control Tool MCT 10 software version 3.23. A license key is required to use the full set of features.
Introduction
Installation Guide | VLT®Safety Option MCB 152
AN327351953089en-000101 / 130R0578
8 | Danfoss A/S © 2020.02
Содержание MCB 152