3 How to Install
3.1.1 How to Install Option in Frequency
Converter
Items required for installing a fieldbus option in the
frequency converter:
•
The fieldbus option
•
Fieldbus option adaptor frame for the FC 300.
This frame is deeper than the standard frame to
allow space for the fieldbus option beneath
•
Strain relief (only for A1 and A2 enclosures)
EtherNet Port1
EtherNet Port2
MCA
121
Option A
EtherNet/IP 130B1
119
MS
MS1
MAC-00-1B-08-00-00-22
MS2
SW.ver.
130B
T797.10
Illustration 3.1
Illustration 3.2
Instructions:
1.
Remove LCP panel from the FC 300.
2.
Remove the frame located beneath and discard it.
3.
Push the option into place. The Ethernet
connectors must be facing upwards.
4.
Remove both knock-outs on the fieldbus option
adaptor frame.
5.
Push the fieldbus option adaptor frame for the FC
300 into place.
6.
Replace the LCP and attach cable.
NOTE
Do not strip and ground the Ethernet cable via the strain
relief-plate! The grounding of screened Ethernet cable is
done through the RJ-45 connector on the option.
NOTE
After installing the MCA 124 EtherCAT option, set
8-01 Control Site
and
8-02 Control Word Source
as follows:
8-01 Control Site
:
[2] Control word only
or
[0] Digital and ctrl.
word
8-02 Control Word Source
:
[3] Option A
3.1.2 Network
It is of high importance that the media chosen for Ethernet
data transmission are suitable. Usually CAT 5e and 6 cables
are recommended for industrial applications. Both types
are available as Unshielded Twisted Pair and Shielded
Twisted Pair. Generally, shielded cables are recommended
for use in industrial environments and with frequency
converters.
A maximum cable-length of 100 m is allowed between
switches.
How to Install
MCA 124 EtherCAT Operating Instruction
MG92A302 - VLT
®
is a registered Danfoss trademark
7
3