8-14 Configurable Control Word CTW
Option:
Function:
[1]
*
Profile
default
[2]
CTW Valid,
active low
[3]
Safe Option
Reset
[4]
PID error
inverse
When enabled, it inverts the resulting error
from the process PID controller. Available
only if "Configuration Mode" is set to
"Surface Winder", "Extended PID Speed OL"
or "Extended PID Speed CL".
[5]
PID reset I
part
When enabled, resets the I-part of the
Process PID controller. Equivalent to
7-40 Process PID I-part Reset
. Available only if
"Configuration Mode" is set to "Surface
Winder", "Extended PID Speed OL" or
"Extended PID Speed CL".
[6]
PID enable
When enabled, enables the extended
process PID controller. Equivalent to
7-50 Process PID Extended PID
. Available only
if "Configuration Mode" is set "Extended PID
Speed OL" or "Extended PID Speed CL".
8-50 Coasting Select
Option:
Function:
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
[0]
Digital
input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial
communication port or fieldbus option.
[2]
Logic AND Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
[3]
*
Logic OR
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-51 Quick Stop Select
Select control of the Quick Stop function via the terminals
(digital input) and/or via the bus.
Option:
Function:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
8-52 DC Brake Select
Option:
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
NOTE
Only selection
[0] Digital input
is available
when
1-10 Motor Construction
is set to
[1]
PM non-salient SPM
.
[0]
Digital
input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial
communication port or fieldbus option.
[2]
Logic AND Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
[3]
*
Logic OR
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-53 Start Select
Option:
Function:
Select control of the frequency converter start
function via the terminals (digital input) and/or
via the fieldbus.
[0]
Digital
input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial
communication port or fieldbus option.
[2]
Logic AND Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
[3]
*
Logic OR
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-54 Reversing Select
Option:
Function:
[0]
Digital
input
Select control of the frequency converter
reverse function via the terminals (digital
input) and/or via the fieldbus.
[1]
Bus
Activates the Reverse command via the serial
communication port or fieldbus option.
[2]
Logic AND Activates the Reverse command via the
fieldbus/serial communication port, AND
additionally via one of the digital inputs.
[3]
*
Logic OR
Activates the Reverse command via the
fieldbus/serial communication port OR via one
of the digital inputs.