Bit 09, Selection of ramp 1/2
Bit 09=‘0’ means that ramp 1 is active (
3-40 Ramp 1 Type
to
3-47 Ramp 1 S-ramp Ratio at Decel. Start
). Bit 09=‘1’ means
that ramp 2 (
3-50 Ramp 2 Type
to
3-57 Ramp 2 S-ramp Ratio
at Decel. Start
) is active.
Bit 10, Data not valid/Data valid
Is used to tell the frequency converter whether the control
word is to be used or ignored. Bit 10=“0” causes the
control word to be ignored, giving the opportunity to turn
off the control word when updating/reading parameters.
Bit 10=“1” causes the control word to be used. This
function is relevant, because the control word is always
contained in the telegram, regardless of which type of
telegram is used.
Bit 11, Relay 01
Bit 11=‘0’ Relay not activated. Bit 11 = ‘1’ Relay 01
activated, provided
Control word bit 11
has been chosen in
5-40 Function Relay
.
Bit 12, Relay 02
Bit 12=‘0’ Relay 02 has not been activated.
Bit 12=‘1’ Relay 02 has been activated, provided
Control
word bit 12
has been chosen in
5-40 Function Relay
.
Bit 13/14, Selection of set-up
Bits 13 and 14 are used to select one of 4 menu set-ups
according to
Set-up
Bit 14
Bit 13
1
0
0
2
0
1
3
1
0
4
1
1
Table 4.9 Menu Set-ups
The function is only possible when
Multi-Set-ups
is selected
in
0-10 Active Set-up
.
NOTICE
In
8-55 Set-up Select
a selection is made to define how Bit
13/14 gates with the corresponding function on the digital
inputs.
Bit 15 Reverse
Bit 15=‘0’ causes no reversing.
Bit 15=‘1’ causes reversing.
NOTICE
In the factory setting reversing is set to
digital
in
. Bit 15 causes reversing only when
Ser.
communication
,
Logic AND
or
Logic OR
is selected.
4.4.1 Status Word according to Frequency
Converter Profile (STW)
→
Illustration 4.3 8-10 Control Word Profile
Bit
Bit value=0
Bit value=1
00
Control not ready
Control ready
01
Drive not ready
Drive ready
02
Coasting
Enable
03
No error
Trip
04
No error
Error (no trip)
05
Reserved
-
06
No error
Trip lock
07
No warning
Warning
08
Speed ≠ reference
Speed = reference
09
Local operation
Bus control
10
Out of frequency limit
Frequency limit ok
11
No operation
In operation
12
Drive ok
Stopped, auto start
13
Voltage ok
Voltage exceeded
14
Torque ok
Torque exceeded
15
Thermal ok
Thermal exceeded
Table 4.10 Staus Word Bits
Explanation of the status bits
Bit 00, Control ready
Bit 00=‘0’ means that the frequency converter has tripped.
Bit 00=‘1’ means that the frequency converter controls are
ready, but that the power component is not necessarily
receiving any power supply (in the event of external 24 V
supply to controls).
Bit 01, Drive ready
Bit 01=‘1’. The frequency converter is ready for operation.
Bit 02, Coasting stop
Bit 02=‘0’. The frequency converter has released the motor.
Bit 02=‘1’. The frequency converter can start the motor
when a start command is given.
Bit 03, No error/Trip
Bit 03=‘0’ means that the frequency converter is not in
fault mode.
Bit 03=‘1’ means that the frequency converter is tripped,
and that a reset signal is required to re-establish operation.
Bit 04, No error/Error (no trip)
Bit 04=‘0’ means that the frequency converter is not in
fault mode.
How to Control
MCA 122 Modbus TCP
24
MG90P202 - VLT
®
is a protected Danfoss trademark
4
4
Содержание MCA 122 Modbus TCP
Страница 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions MCA 122 Modbus TCP ...
Страница 2: ......
Страница 13: ...Illustration 2 7 How to Install MCA 122 Modbus TCP MG90P202 VLT is a protected Danfoss trademark 9 2 2 ...
Страница 46: ...www danfoss com drives MG90P202 130R0446 MG90P202 Rev 2013 05 02 ...