manualshive.com logo in svg
background image

2 | © Danfoss | DCS (CC) | 2018.06

8510283P01B - FRCC.PI.047.A3.02

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This 
also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trade-
marks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

5 – Leak detection

 Never pressurize the circuit with oxygen or dry 

air. This could cause fire or explosion.
 •  Do not use leak detection dye.
 •  Perform a leak detection test on the complete 

system.

 •  The low side test pressure must not exceed 31 bar 

/450 psi.

 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

 •  Never use the compressor to evacuate the system.
 •  Connect a vacuum pump to both the LP & HP 

sides.

 

• 

 

Pull down the system under a vacuum of 

 

500 µm Hg (0.67 mbar) / 0.02 inch Hg absolute.

 •  Do not use a megohmmeter nor apply power to 

the compressor while it is under vacuum as this 
may cause internal damage.

7 – Electrical connections

 •  Switch off and isolate the main power supply.
 •  All electrical components must be selected as per 

local standards and compressor requirements.

 •  Refer to page 1 for electrical connections details. 

For three phase applications, the terminals are 
labeled T1, T2, and T3.

 •  Danfoss scroll compressors will only compress gas 

while rotating counter-clockwise (when viewed 
from the compressor top). Three-phase motors, 
however, will start and run in either direction, 
depending on the phase angles of the supplied 
power. Care must be taken during installation to 
ensure that the compressor operates in the correct 
direction.

 •  Use ø 4.8 mm / #10 - 32 screws and ¼” ring 

terminals for the power connection with ring 
connect screw terminal (C type). Fasten with 3 Nm 
torque.

 •  Use a self tapping screw to connect the compressor 

to earth.

8 – Filling the system

 •  Keep the compressor switched off.
 •  Keep the refrigerant charge below the indicated 

charge limits if possible. Above this limit; protect 
the compressor against liquid flood-back with a 
pump-down cycle or suction line accumulator.

 •  Never leave the filling cylinder connected to the 

circuit.

Compressor models

Refrigerant charge limit 

LLZ013-015-018

4.5 kg / 10 lb

LLZ024-034

7.2 kg / 16 lb

9 – Verification before commissioning

 Use safety devices such as safety pressure switch 

and mechanical relief valve in compliance with both 
generally and locally applicable regulations and 

safety standards. Ensure that they are operational 
and properly set. 

 Check that the settings of high-pressure switches 

don’t exceed the maximum service pressure of any 
system component.
 •  A low-pressure switch is recommended to avoid 

low pressure operation. 

Minimum setting for R404A/R507 1.3 bar (absolute) / 19 psia

Minimum setting for R452A

1.2 bar (absolute) / 17.6 psia

Minimum setting for R448A/R449A 1.0bar (absolute) / 14.5psia

 •  Verify that all electrical connections are properly 

fastened and in compliance with local regulations.

 •  When a crankcase heater is required, it must be 

energized at least 24 hours before initial start-up 
and start-up after prolonged shutdown. 

10 – Start-up

 •  Never start the compressor when no refrigerant is 

charged.

 •  

Do not provide any power to the compresor 
unless suction and discharge service valves are 
open, if installed.

 •  Energize the compressor. It must start promptly. 

If the compressor does not start, check wiring 
conformity and voltage on terminals.

 •  

Eventual reverse rotation can be detected by 
following phenomena; the excessive noise, 
no pressure differential between suction 
and discharge, and line warming rather than 
immediate cooling. A service technician should 
be present at initial start-up to verify that supply 
power is properly phased and that the compressor 
is rotating in the correct direction. For LLZ 
compressors, phase monitors are required for all 
applications. 

  •  If the internal overload protector trips out, it must 

cool down to 60°C / 140°F to reset. Depending on 
ambient temperature, this may take up to several 
hours.

11 – Check with running compressor

 Check current draw and voltage. Measurement 

of amps and volts during running conditions must 
be taken at other points in the power supply, not in 
the compressor electrical box.
 •  Check suction superheat to reduce risk of slugging.
 •  Observe the oil level in the sight glass (if provided) 

for about 60 minutes to ensure proper oil return to 
the compressor.

 •  Respect the operating limits.
 

• 

 

 

Check all tubes for abnormal vibration. 
Movements in excess of 1.5 mm / 0.06 in require 
corrective measures such as tube brackets.

 • 

 

When needed, additional refrigerant in liquid 
phase may be added in the low-pressure side as far 
as possible from the compressor. The compressor 
must be operating during this process.

 •  Do not overcharge the system.
 •  Never release refrigerant to atmosphere.

 • 

 

Before leaving the installation site, carry out 
a general installation inspection regarding 
cleanliness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference for 
future inspections.

12 – Maintenance

 Internal pressure and surface temperature 

are dangerous and may cause permanent injury. 
Maintenance operators and installers require 
appropriate skills and tools. Tubing temperature 
may exceed 100°C / 212°F and can cause severe 
burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 
regulations are performed.
To prevent system related compressor problems, 
following periodic maintenance is recommended:
 •  

 

Verify that safety devices are operational and 
properly set.

 •   Ensure that the system is leak tight.
 •   Check the compressor current draw.
 •   Confirm that the system is operating in a way 

consistent with previous maintenance records and 
ambient conditions.

 • 

 

 

Check that all electrical connections are still 
adequately fastened.

 •   Keep the compressor clean and verify the absence 

of rust and oxidation on the compressor shell, 
tubes and electrical connections.

 •  Acid / moisture content in system and oil should 

be checked regularly.

13 - Warranty

Always transmit the model number and serial 
number with any claim filed regarding this product.
The product warranty may be void in following 
cases:
  •   Absence  of  nameplate.
 

• 

 

 

External modifications; in particular, drilling, 
welding, broken feet and shock marks.

 •   Compressor opened or returned unsealed.
 • 

 

 

Rust, water or leak detection dye inside the 
compressor.

 •   Use of a refrigerant or lubricant not approved by 

Danfoss.

 •   Any deviation from recommended instructions 

pertaining to installation, application or 
maintenance.

 •   Use in mobile applications.
 •   Use in explosive atmospheric environment.
 •   No model number or serial number transmitted 

with the warranty claim.

14 – Disposal

Danfoss recommends that compressors 
and compressor oil should be recycled 
by a suitable company at its site.

Отзывы: