manualshive.com logo in svg
background image

Instructions

8510306P01AB - AN382129347378en-000101 | 3

© Danfoss | Climate Solutions | 2021.08

9 – Verification before commissioning

 Use safety devices such as safety pressure switch 

and mechanical relief valve in compliance with both 
generally and locally applicable regulations and 
safety standards. Ensure that they are operational 
and properly set. 

 Check that the settings of high-pressure switches 

don’t exceed the maximum service pressure of any 
system component.
 •  A low-pressure switch is recommended to avoid 

low pressure operation. 

Minimum setting for R454C/R455A 1.0bar (absolute) / 14.5psia

 •  Verify that all electrical connections are properly 

fastened and in compliance with local regulations.

 •  When a crankcase heater is required, it must be 

energized at least 24 hours before initial start-up 
and start-up after prolonged shutdown. 

10 – Start-up

 •  Never start the compressor when no refrigerant is 

charged.

 •  Do not provide any power to the compresor 

unless suction and discharge service valves are 
open, if installed.

 •  Energize the compressor. It must start promptly. 

If the compressor does not start, check wiring 
conformity and voltage on terminals.

 •  Eventual reverse rotation can be detected by 

following phenomena; the excessive noise, 
no pressure differential between suction 
and discharge, and line warming rather than 
immediate cooling. A service technician should 
be present at initial start-up to verify that 
supply power is properly phased and that the 
compressor is rotating in the correct direction. For 
LLZ compressors, phase monitors are required for 
all applications. 

  •  If the internal overload protector trips out, it must 

cool down to 60°C / 140°F to reset. Depending on 
ambient temperature, this may take up to several 
hours.

11 – Check with running compressor

 Check current draw and voltage. Measurement 

of amps and volts during running conditions must 
be taken at other points in the power supply, not in 
the compressor electrical box.
 

• 

 

Check suction superheat to reduce risk of 
slugging.

 •  Observe the oil level in the sight glass (if provided) 

for about 60 minutes to ensure proper oil return to 
the compressor.

 •  Respect the operating limits.
 

• 

 

 

Check all tubes for abnormal vibration. 
Movements in excess of 1.5 mm / 0.06 in require 
corrective measures such as tube brackets.

 •  

When needed, additional refrigerant in liquid 
phase may be added in the low-pressure side as far 
as possible from the compressor. The compressor 
must be operating during this process.

 •  Do not overcharge the system.
 •  Never release refrigerant to atmosphere.
 •  

Before leaving the installation site, carry out 
a general installation inspection regarding 
cleanliness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference for 
future inspections.

12 – Maintenance

 Internal pressure and surface temperature 

are dangerous and may cause permanent injury. 
Maintenance operators and installers require 
appropriate skills and tools. Tubing temperature 
may exceed 100°C / 212°F and can cause severe 
burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 
regulations are performed.
To prevent system related compressor problems, 
following periodic maintenance is recommended:
 •   Verify that safety devices are operational and 

properly set.

 •   Ensure that the system is leak tight.
 •   Check the compressor current draw.
 •   Confirm that the system is operating in a way 

consistent with previous maintenance records 
and ambient conditions.

 •  

 

Check that all electrical connections are still 
adequately fastened.

 •   Keep the compressor clean and verify the absence 

of rust and oxidation on the compressor shell, 
tubes and electrical connections.

 •  Acid / moisture content in system and oil should 

be checked regularly.

13 - Warranty

Always transmit the model number and serial 
number with any claim filed regarding this product.
The product warranty may be void in following 
cases:
  •   Absence  of  nameplate.
 

• 

 

 

External modifications; in particular, drilling, 
welding, broken feet and shock marks.

 •   Compressor opened or returned unsealed.
 •  

 

Rust, water or leak detection dye inside the 
compressor.

 •   Use of a refrigerant or lubricant not approved by 

Danfoss.

 •   Any deviation from recommended instructions 

pertaining to installation, application or 
maintenance.

 •   Use in mobile applications.
 •   Use in explosive atmospheric environment.
 •   No model number or serial number transmitted 

with the warranty claim.

14 – Disposal

Danfoss recommends that compressors 
and compressor oil should be recycled 
by a suitable company at its site.

Отзывы: