![Danfoss LLS 4000 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/danfoss/lls-4000/lls-4000_installation-manual-quick-start_508478005.webp)
© Danfoss | DCS (ms) | 2020.05
AN317523977313en-000201 | 5
General specifications
Electrical data
Supply
24 V DC +/-25%, 80 mA
Standard power supply of type: SELV (Separated Extra Low Voltage)
with current limit of max. 8A.
Relay (Solid state)
Max 30 V DC, 200 mA.
Same power supply as to supply can be used.
Observe:
In applications with request for SIL2, another separate SELV power
supply may be needed.
Max. cycles: 1.000.000
Mechanical Data
Max. medium viscosity
5000 cps
Max. working pressure
65 bar (943 psi)
Ambient temperature range
-40 °C to +65 °C (-40 °F to +149 °F)
Medium temperature range
-50 °C to +120 °C (-58 °F to +248 °F)
Operating environment
Pollution degree 3, altitude 2000 max., outdoor use
Connection type
G ¾ in. or NPT ¾ in.
Weight
350 g (0.77 lbs.)
Approved media
Refrigerants
R717/NH3 (Ammonia): -50 °C to +105 °C (-58 °F to +221 °F)
R22: -50 °C to +86 °C (-58 °F to +187 °F)
R404A: -50 °C to +63 °C (-58 °F to +145 °F)
R410A: -50 °C to +61 °C (-58 °F to +142 °F)
R134A: -50 °C to +91 °C (-58 °F to +196 °F)