background image

The grey
side of the
ECL Card

Basic set-up

The grey

side of the 

ECL Card

Basic set-up

4  Proportional band, Xp

Circuit

Setting range

Factory setting

I / II

1 ... 250 K

80 / 80 K

Set the proportional band. 
A higher value will result in a stable but slow 
control of the flow temperature.

5  Integration time constant, Tn

Circuit

Setting range

Factory setting

I / II

5 ... 999 sec.

30 / 20 sec.

Set a high integration time constant to obtain a 
slow but stable reaction to deviations.

A small integration constant will make the 
controller react fast but with less stability

6  Running time of the motorized control valve

Circuit

Setting range

Factory setting

I / II

5 ... 250 sec.

35 / 15 sec.

Set the running time of the motorized control 
valve according to the example. This is the time it 
takes the controlled unit to move from fully closed 
to fully open position.

How to calculate the running time of a motorized 

control valve 

The running time of the motorized control valve is calculated 
using the following methods:

Seated valves

Running time   =  Valve stroke (mm) x actuator speed (sec. / mm)

Example:  

 

5.0 mm x 15 sec. / mm = 75 sec.

Rotating valves

Running time   =  Turning degrees x actuator speed (sec. / degr.)

Example: 

 

90 degrees x 2 = 180 sec.

Control parameters -

lines 4-7

26a

7  Neutral zone, Nz

Circuit

Setting range

Factory setting

I / II

0 ... 9 K

3 / 3 K

Set the neutral zone to a high value if you can 
accept a high variation in flow temperature. 
When the actual flow temperature is within the 
neutral zone, the controller does not activate the 
motorized valve.

The neutral zone is symmetrical around the desired flow 
temperature value, i.e. half the value is above and half the value is 
below this temperature.

Control parameters (lines 4-7) are overruled if thermo actuator is 
chosen (OFF).

If you want to tune the PI regulation precisely, you can 

use the following method:

•  Set the integration time (line 5) to its max. value 
  (999 sec.).

•  Decrease the value for the proportional band (line 4) until the 

system starts hunting with a constant amplitude (it might be 
necessary to force the system by setting an extreme value).

•  Find the critical time period on the temperature recording or 

use a stop watch.

       Temp.

 

 

 

    Critical time period

 

 

 

 

 

 

 

                  

Time

This time period will be characteristic for the system, and you can 
evaluate the settings from this critical period.

Integration time 

=  0.85 x critical time period 

Proportional band  =   2.2 x proportional band value in the
 

 

critical time period. 

If the regulation seems to be too slow, you can decrease the
proportional band value by 10%.

Make sure there is a consumption when you set the parameters.

26b

Содержание L66

Страница 1: ...T2 02 2006 12 VI JD T2 02 2006 12 www danfoss com User s Guide Installer s Guide www danfoss com ECL Comfort Installer s Guide ECL Comfort User s Guide 087R8172 VIJDT202 087R8172 VIJDT202 Mixing and D...

Страница 2: ...ion pump 2 DHW circuit II M1 Motorized control valve circuit I M2 Motorized control valve circuit II This guide is associated with ECL Card 087B4875 Installer By Date Controller mode Manual operation...

Страница 3: ...17 Setting the time and date line A 18 Monitoring temperatures and system units line B 19 Manual control line B 20 Setting the heat curve line C 21 Heating cut out line 1 22 Flow temperature limits li...

Страница 4: ...Typically the ow temperature is adjusted according to your requirements The ow temperature sensor S3 is the most important sensor The desired ow temperature at S3 is calculated in the ECL controller...

Страница 5: ...n below nd the diagram which has the best resemblance with your system and make your own combinations The functions can only be realized with ECL Comfort 301 and as of controller version 2 00 10 1 Ind...

Страница 6: ...d position the controller in the box Secure the controller with the xing screw Mounting on a DIN rail Mounting kit Order code No 087B1145 A mounting kit is necessary to mount the box with the controll...

Страница 7: ...c 7 M2 Actuator close circuit II 0 2 A 230 V a c 8 230 V a c supply voltage for M2 circuit II 9 P1 1 Circulation pump I for heating circuit I 4 2 A 230 V a c 10 230 V a c supply for pump relay R1 11...

Страница 8: ...ion in your system The temperature sensor mentioned below are sensors used for the ECL Comfort 200 and 300 series which not all will be needed for your application Outdoor temperature sensor ESMT The...

Страница 9: ...n be used for override purposes section 32 line 141 Connection example without ECA 9010 If the override switch has goldplated contacts you can choose one of the following solutions or a combination of...

Страница 10: ...everal controllers are installed in the system you can write a title on the ECL Card with a permanent ink pen Do not remove the ECL Card while copying The data on the ECL Card can be damaged When you...

Страница 11: ...sted Use the shift button to switch between the options The circuit selector shifts between circuit I and II You can adjust all settings and service parameters individually Update of the ECL Card afte...

Страница 12: ...25 150 C 805 845 883 922 961 1000 1039 1078 1117 1155 1194 1232 1271 1309 1347 1385 1423 1462 1501 1539 1578 C 50 40 30 20 10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 Monitoring temperatur...

Страница 13: ...heat curve no matter if a room temperature sensor is connected or not Floor heating systems This controller is factory set for radiator systems which typically are high ow temperature systems To cont...

Страница 14: ...limit The heating system switches ON again when the outdoor temperature and the accumulated outdoor temperature become lower than the set limit The heating cut out is only active when the controller m...

Страница 15: ...set to 40 The in uence at min limitation left corner of the display is set to 0 Heat curve H is 1 8 Result The desired ow temperature is changed by 2 x 40 x 1 8 x 0 1 14 4 degrees 23b B Reference roo...

Страница 16: ...rees x 2 180 sec Control parameters lines 4 7 26a 7 Neutral zone Nz Circuit Setting range Factory setting I II 0 9 K 3 3 K Set the neutral zone to a high value if you can accept a high variation in ow...

Страница 17: ...close and that required pumps fans dampers and burners start and stop when operated manually See section 19 Having completed the manual operation check choose scheduled operation as controller mode C...

Страница 18: ...min 0 max 40 See section 23 4 Proportional band Xp 1 250 K 80 K See section 26 5 Integration time constant Tn 5 999 sec 30 sec See section 26 6 Running time of the motorized control valve 5 250 sec 3...

Страница 19: ...0 0 37 Time constant for return temperature limitation OFF 1 50 25 43 Parallel operation of DHW and heating circuits OFF 1 99 K OFF K 52 Closed valve normal operation ON OFF OFF 81 Time constant of i...

Страница 20: ...e service parameters 32 10 Choice of room panel remote control Circuit Setting range Factory setting I 1 2 1 Decides the communication with the room panel or remote control Please note that the room p...

Страница 21: ...lowly 14 Optimizing time constant Circuit Setting range Factory setting I OFF 10 59 OFF Optimizes the start and stop times for the comfort temperature period to obtain the best comfort at the lowest e...

Страница 22: ...ler T ow ref I the temperature of the master will be increased accordingly T ow ref II the setting line 17 The function of line 17 can compensate for heat losses between master and slave controlled sy...

Страница 23: ...FF The pump exercise is not active 23 Valve exercise Circuit Setting range Factory setting I ON OFF OFF Exercises the valve to avoid blocking in periods without heat demand ON The valve receives a sig...

Страница 24: ...ower limit Y axis Circuit Setting range Factory setting I 10 110 C 60 C Set the return temperature limitation see drawing Set the return temperature Y coordinate for the lower limit The corresponding...

Страница 25: ...n uence is set to 3 0 The actual return temperature is 2 degrees too low Result The desired ow temperature is changed by 3 0 x 2 6 degrees Normally the setting in line 36 is 0 in district heating syst...

Страница 26: ...nt parallel operation i e the desired heating temperature depends on the DHW demand Choose how much the DHW temperature circuit II can drop before the desired heating temperature circuit I has to be d...

Страница 27: ...tion example with ECA 9010 used if the override switch does not have gold plated contacts 16 Brown 15 Red Green S1 S6 The ECA 9010 module is powered by the system device bus which means that the bus m...

Страница 28: ...ion time When the chosen pressure stabilization time is too short the active pump will stop immediately after the pressure stabilization time has elapsed 153 Changeover delay TCH Circuit Setting range...

Страница 29: ...sired ow temperature to the master 15 The controller is master The master sends information about the outdoor temperature S1 system time and the DHW demand signal The master receives the desired ow te...

Страница 30: ...ECL Card Do not remove the ECL Card while copying The data on the ECL Card can be damaged If you have copied your personal settings to the ECL Card you cannot restore the factory settings Copy persona...

Страница 31: ...circuit for heating the domestic hot water DHW 7b Humidity relative This value stated in refers to the indoor moisture content compared to the max moisture content The relative humidity is measured by...

Страница 32: ...is not too high See section 22 The temperature is unstable Check that the ow temperature sensor is correctly connected and in the right place Adjust the control parameters section 26 If the controlle...

Страница 33: ...ns to display line C section 1 further changes are not possible the controller continues its operation When the ECL Card is inserted with the yellow side facing you the controller can be operated agai...

Страница 34: ...comfort period Shift to next changeover point and adjust accordingly Change the schedule for circuit II Select circuit II to view or change the schedule Use the same method for changes as for circuit...

Страница 35: ...on Use this mode when you are away on holiday etc Standby The heating circuit is stopped The system is still protected against frost In the DHW circuit however the DHW temperature is controlled accord...

Страница 36: ...The controller automatically reverts to display C if the card has been reinserted or the power supply has been interrupted If the temperature value is displayed as the sensor in question is not connec...

Страница 37: ...ntages of the ECL Comfort controller system are Secure control and the optimum use of energy resources Control of system temperatures according to seasonal changes and variations in outdoor temperatur...

Страница 38: ...that are relevant to your ECL Comfort controller are included here Installer s Guide Grey sections 10 and onwards Turn the guide over The functions can only be realized with ECL Comfort 301 and as of...

Отзывы: