Contact function test (Manual trip)

When the electrical leads are connected the contact function 
can be manually tested regardless of pressure condition in 
the system. The manual trip lever is located in the left side 
of the KPU. It must be operated with fingers only. Do not use 
screwdriver as it will damage the switch.

NOTE: 

While operating the manual trip on KPU  
switches with manual reset it is necessary  
to push the reset knob.

NOTE: 

Adjust the pressure switch with settings specified by the 
manufacturer of the controlled quipment. 
Do not exceed the pressure ratings of the controlled 
equipment or any of its components when checking 
pressure switch operation or operating the controlled 
equipment.
Do not adjust pointers beyond the highest or lowest 
indicator marks on the scale plate, as this may cause
inaccurate switch operation.

A: 

Manual trip. Press the lever up. USE FINGERS ONLY!

B: 

Manual reset button  

(available only for contols with manual reset function)

C: 

Terminal block

D: 

Grounding screw

A:

 Differential adjusting screw

B: 

Locking plate

C:

 Range adjusting screw

D:

 Cover screw

Adjustment

Before adjustment, loosen the locking plate.
For setting use the Universal Refrigeration Wrench.

Wire dimensions: 10 AWG max.
Cable entry: 

7

/

8

 in. cable entry for ½ in. male pipe thread 

connection (conduit boss) or similar (Pg13.5 or Pg16) screwed 
cable entry.

Wiring Option A:

– Low Pressure Switch Cut Out on pressure fall
– Condenser Fan Cycling

Wiring Option B:

– High Pressure Switch Cut Out on pressure rise

Load

~Line