Installation guide

Thermostat

Type KPU

 

DKRCC.PI.CA0.F1.22 / 520H10107 

1

06

0R

97

71

06

0R

97

71

Application

KPU 19 thermostats are used 

for temperature regulation 

in refrigeration, freezing, air  

conditioning, ventilating and heating 

systems.

KPU 19 thermostats are fitted with 

Single-Pole Double-Throw  (SPDT) 

or Single-Pole Single-Throw (SPST) 

contact system.

The standard KPU 19 enclosure is rated 

NEMA ~ 1.

NEMA ~ 1 is obtained when the 

thermostat is mounted on a flat 

surface with all unused holes covered.

Type

Regulating 

range 

[°F]

Differential 

∆T [°F]

Bulb size 

[in.]

Capillary tube 

length 

[in.]

Max. bulb 

temperature

 [°F]

Ambient

temperature

[°F]

Contact 

type

Reset 

type

Code no.

KPU 19

-30 

 80

3.6 

 12.6 

3

/

8

  x  4 

1

/

2

120

140

-31 

 

158

SPDT

Auto.

060L2150

KPU 19

-30 

 80

3.6 

 12.6

3

/

8

  x  4 

1

/

2

80

140

-31 

 

158

SPST 

(close on 

temp. rise)

Auto.

060L2151

KPU 19

-30 

 80

3.6 

 12.6

-

Air coil / Room 

sensor

140

-31 

 

140

SPDT

Auto.

060L2152

 

Product specification

Important

The KPU 19 thermostat is designed 

only for use as a temperature 

regulating operating control. It is the 

responsibility of the installer to verify 

that other necessary safety controls 

are installed and functioning properly 

as intended by the original equipment 

manufacturer or system design.

Thermostat bulb types

Dimensions [in.]