Electrical connection 

The KP-E pressure switch placed in explosive zone must always be 

wired through reliable Ex zener barrier, placed outside ex-zone, 

to ensure insufficient energy supply to cause the ignition of 

surrounding atmosphere by an electrical spark or the heating of 

components of circuitry.

The equipment to be used for electrical load limiting must always 

be approved for use in the zone concerned.

Cables and cable entries approved for the application must be 

used and can not be in contact with sharp edges. Cables must be 

connected with adequate stress relief that way that pulling forces 

can not be carried throug the cable to the terminal. 

Note:

A particular system can be classified in different zones, for 

different parts of the system.

EX - zone

Non EX - zone

Electrical data for intrinsically safe 

specification (for all KP-E types):

Product marking

Danf

oss

60-8070.11

Pi max:  1 W
Ui max: 30 V
Ii max:  0.1 A
Ci max: 0.5 nF
Li max:  0.2 µH

II3G

Ex ic IIB T6Gc

Must be used with certified Ex ic barrier (product matching) satisfying the input parameters.

Intrinsic safety protection method

KP-E

Signal

EX certified 

Zenner 

barrier

Contact function

KP 1E

KP 7EW,

KP 7EB

Contact 1-4 opens on pressure drop:

Contact 1-2 opens on pressure rise:

Manual trip function

Automatic reset

Manual reset

Range

Diff.

6 mm

(15/64 in)