Reset options
© Danfoss A/S (AC-MCI / jmn), 2012-11
DKRCI.PI.C00.C1.22 / 520H6064
3
LP
man.
LP
auto.
LP
auto.
LP
man.
HP
man
HP
man
HP
auto.
HP
auto.
Manual tripping
(Electrical contacts/wiring test)
Note:
On controls with LP and/or HP man. reset, push corresponding
LP and/or HP man. reset knob during tripping.
Trip:
use FINGERS ONLY! (Do NOT use screwdriver)
To resume control operation after safety cut-out,
push man. reset knob as indicated.
Note:
LP man. reset is possible only after system pressure
has risen above cut-in value.
HP man. reset is possible only after system pressure
has dropped below cut-out value.
Manual reset
Convertible reset
Note:
Do not select automatic reset if safety
of the system requires manual reset.
Note:
Selected reset configuration may be protected
against unauthorized actions applying a seal.
Insert a screwdriver into the slot on the lock disc and turn it
to desired reset configuration. Do not turn the screw on the
lock disc as it may damage the convertible reset mechanism.
LP side
HP side
Adjustment spindle(s) location
Use screw
driver only