Connections

Assembly

Wiring

All wiring should conform to the National

Electrical Code and local regulations.

SPDT

Controls with low pressure (LP) signal

Terminal block

Controls with low pressure (LP)  

and high pressure (HP) signal)

Terminal block

CAUTION

:

Use terminal screws furnished  

in the contact block.

Use tightening torque 20 lb. in (2.3 Nm).

Use copper wire only.

Low pressure (LP) side:

A-C close on LP rise

A-C open on LP drop

High pressure (HP) side:

A-C open on HP rise

A-C close on HP drop

LP signal option:

A-B close on LP drop

See label for current wiring inside cover.

CAUTION: 

Use terminal screws furnished  

in the contact block.

Use tightening torque 20 lb. in (2.3 Nm).

Use copper wire only.

Low pressure (LP) side:

A-C close on LP rise

A-C open on LP drop

High pressure (HP) side:

A-C open on HP rise

A-C close on HP drop

LP signal option:

A-B close on LP drop

HP signal option:

A-D close on HP rise

Function

Contact load ratings

See label inside cover

120 V AC

16 FLA, 96 LRA

240 V AC

8 FLA, 48 LRA

240 V DC

12 W pilot duty

CAUTION:

Disconnect power supply before wiring connections are made or service to avoid possible electrical shock or damage 

to equipment. Do never touch live parts with your fingers or with any tool. 

  = Load

  = Signal option

  = Bellows movement  

on pressure rise

  = Bellows movement  

on pressure drop

Note

!

© Danfoss | DCS (jmn) | 2016.10

2 | 520H11520 | DKRCC.PI.CA0.B3.22

Содержание KP 15

Страница 1: ...ments KP 15 man LP man HP reset KP 15 KP 17B auto LP man HP reset KP 15 KP 17W KP 25 auto LP auto HP reset Enclosure CAUTION The mounting panel must be plane to avoid damage of control CAUTION Do not mount the control in a position where dirt sediment or oil will affect the operation of the control CAUTION Do not install these controls on ammonia systems Refrigerants R22 R134a R404A R407A R407C R4...

Страница 2: ... terminal screws furnished in the contact block Use tightening torque 20 lb in 2 3 Nm Use copper wire only Low pressure LP side A C close on LP rise A C open on LP drop High pressure HP side A C open on HP rise A C close on HP drop LP signal option A B close on LP drop HP signal option A D close on HP rise Function Contact load ratings See label inside cover 120 V AC 16 FLA 96 LRA 240 V AC 8 FLA 4...

Страница 3: ... out push man reset knob as indicated Note LP man reset is possible only after system pressure has risen above cut in value HP man reset is possible only after system pressure has dropped below cut out value Manual reset Convertible reset Insert a screwdriver into the slot on the lock disc and turn it to desired reset configuration Do not turn the screw on the lock disc as it may damage the conver...

Страница 4: ... 10 psi 20 psig 2 1 bar 0 7 bar 1 4 bar CUT OUT DIFF CUT IN 12 psig 10 psi 22 psig 0 8 bar 0 7 bar 1 5 bar Example CUT OUT DIFF CUT IN 203 psig 58 psi 145 psig 14 bar 4 bar 10 bar Low pressure LP side setting High pressure HP side setting Setting KP 15 KP 17W KP 17B and KP 25 with LP auto reset only KP 15 KP 17W KP 17B and KP 25 with HP auto or man reset KP 15A with LP man reset only KP 15A with c...

Отзывы: