© Danfoss A/S (AC-MCI / jmn), 2012-11 

DKRCC.PI.C00.E1.22 / 520H6070 

3

Manual reset KP 1, KP 5, KP 7B

Setting 

(see also “Wiring”)

KP 1 (auto reset), KP 2, KP 5, KP 7W, KP 7B

1.

 Adjust range spindle to desired HIGH SET POINT (HSP)

2.

 Adjust differential spindle to desired DIFFERENTIAL (DIFF.)

1.

 Adjust range spindle to desired LOW SET POINT (LSP)

2.

 DIFFERENTIAL is fixed Value printed on scale plate

HIGH SET POINT minus DIFFERENTIAL equals LOW SET POINT

Example:

Example:

LOW SET POINT plus DIFFERENTIAL equals HIGH SET POINT  

KP 1 (manual reset ONLY)

HSP 

–  DIFF.  =   LSP

30 psig  –  20 psi  =  10 psig

(2.1 bar) 

(1.4 bar) 

(0.7 bar)

LSP 

+  DIFF.  =   HSP

12 psig  +  10 psi  =  22 psig

(0.8 bar) 

(0.7 bar) 

(1.5 bar)

If terminals 1-4 are used:   CUT-IN 

= HSP

 

CUT-OUT  = LSP

If terminals 1-2 are used:  CUT-IN 

= LSP

 

CUT-OUT  = HSP

Note:

KP 5 (manual reset) and KP 7B have fixed diff.

Value printed on scale plate.

Adjustment

Note:

Remove lockplate before adjustment.

Replace lockplate after adjustment (if desired).

See instruction printed on top of control

KP 1: 3 psi (0.2 bar)/rev. 

KP 2: 1.5 psi (0.1 bar)/rev. 

KP 5: 4 psi (0.3 bar)/rev. 

KP 7W: 7 psi (0.5 bar)/rev. 

Range

Increase 

360

°

Decrease

360

°

Increase 

360

°

Decrease

360

°

6 mm

(

15

/

64

 in.)

Differential

KP 1: 10 psi (0.7 bar)/rev. 

KP 2: 7 psi (0.5 bar)/rev. 

KP 5, 7W, 7B: 33 psi (2.3 bar)/rev. 