Non-Volatile Parameters
After volatile parameters are configured, the function block sends a request for the configuration CRC to

the I/O module.

If this number matches the locally calculated value, then the configurations stored on the I/O module
match those set in the function block. If the numbers do not match, then all configuration commands are
sent and the CRC is requested again.

You can use the PLUS+1

®

 Service Tool to access all non-volatile parameters on the I/O module.

Timing Configurations
Timing for messages to and from the I/O module is established after all other configurations are sent.

CAN Bus Load
Adjust the average amount of message transmissions on the CAN bus to allow for bursts and other

increased message transmission situations.

Any CAN bus has a maximum message transmission capacity. So, to allow for situations that can cause
increases in messages, minimize the CAN bus load.

The CAN bus load is the average amount of message transmission on a CAN bus. Use the PLUS+1

®

 CG150

USB/CAN gateway and CANKing software to view CAN bus loads.

PLUS+1

®

 I/O modules communicate with their associated controllers over a CAN bus. System developers

can adjust I/O module RepTime and TimeOut parameters to manage CAN bus loading. Increasing these
times reduces the CAN bus load. Decreasing these times increases CAN bus load.

CAN Message Identifiers

The function block uses the following message identifiers to enable communication between the

controller and the I/O module.

I/O Module CAN Message Identifiers

CAN Shield Voltage [mV]

N1

KWP2000 Node

Tx ID

Rx ID

0 – 299

0

0

0x180

0x300

300 – 599

1

8

0x188

0x308

600 – 899

2

16

0x190

0x310

900 – 1199

3

24

0x198

0x318

1200 – 1499

4

32

0x1A0

0x320

1500 – 1799

5

40

0x1A8

0x328

1800 – 2099

6

48

0x1B0

0x330

2100 – 2399

7

56

0x1B8

0x338

2400 – 2699

8

64

0x1C0

0x340

2700 – 2999

9

72

0x1C8

0x348

3000 – 3299

10

80

0x1D0

0x350

3300 – 3599

11

88

0x1D8

0x358

3600 – 3899

12

96

0x1E0

0x360

3900 – 4199

13

104

0x1E8

0x368

4200 – 4499

14

112

0x1F0

0x370

4500 –

15

120

0x1F8

0x378

User Manual

PLUS+1® Compliant IX012-010 Function Block

IX012-010 Function Block

 

10 | 

©

 Danfoss | July 2018

11063398 | AQ00000107en-US0101

Содержание IX012-010

Страница 1: ...User Manual PLUS 1 Compliant IX012 010 Function Block www danfoss com...

Страница 2: ...Revision history Table of revisions Date Changed Rev July 2018 Rebranding 0101 June 2009 AA User Manual PLUS 1 Compliant IX012 010 Function Block 2 Danfoss July 2018 11063398 AQ00000107en US0101...

Страница 3: ...s and Signal Overview 8 Configuring Communications 9 Variable Addressing Mode 9 Predefined Addressing Mode 9 Fixed Addressing Mode 9 Volatile Parameters 9 Non Volatile Parameters 10 Timing Configurati...

Страница 4: ...e The CAN messages use 11 bit identifiers in this mode 2 Fixed ID addressing mode The I O module Tx and Rx message identifiers are determined directly by setting Tx ID and Rx ID The CAN messages use e...

Страница 5: ...ines how often the Power Sensor Power and CAN Shield input values are transmitted from the I O module 1000 is 1 ms RepTime_DigAn_In U16 0 65535 Determines how often the DigIn and AnIn values are trans...

Страница 6: ...h Supply Voltage The internal Pull Up resistor is connected to an internal 5 V The internal Pull Down resistor is connected to Ground PinConfig1 U16 Output 0 3 Sets the maximum input voltage to allow...

Страница 7: ...ear in both the Input and Output buses Signal Type Direction Range Description CAN Bus CommStatus U16 Input 1 8 255 Current status of communication with the I O module 0 CAN message transmission is di...

Страница 8: ...on block requires I O module hardware using protocol version 2 00 to 2 99 ProtocolVersion U16 Input 0 65535 I O communication protocol version used by the I O module hardware 200 is version 2 00 Conne...

Страница 9: ...module In this mode the I O module reads the N1 value stored in non volatile memory EEPROM Because the function block and the I O module use different default addressing modes as long as the N1 value...

Страница 10: ...ion on a CAN bus Use the PLUS 1 CG150 USB CAN gateway and CANKing software to view CAN bus loads PLUS 1 I O modules communicate with their associated controllers over a CAN bus System developers can a...

Страница 11: ...nfigured but a second I O module has a similar configuration Review configuration and make changes to the other I O modules Incompat_Protocl is true The firmware on the I O module uses a version of th...

Страница 12: ...lutions ApS Nordborgvej 81 DK 6430 Nordborg Denmark Phone 45 7488 2222 Danfoss Power Solutions US Company 2800 East 13th Street Ames IA 50010 USA Phone 1 515 239 6000 Danfoss Power Solutions Trading S...

Отзывы: