User Guide
|
Intelligent Purging System (IPS 8) for Ammonia - Technical data, installation and use
18 | BC306932151284en-000201
© Danfoss | DCS (ms) | 2020.01
Configuring using the LCD
By pressing the main menu will show up with the options below
Table 02
Main menu navigation
Main Menu
Submenu
Submenu/status Submenu/status
Min
Max
Default Description
Label
Alarms
Active alarms
No alarm
up to 15 alarms
(see table
below)
Up to 15 possible alarms listed by arrow up/down
Reset alarms
Reset all actual alarms
Log history
View log history
Clear log
history
Clear log history
Login
Password
***
200
N/A
Start
Turn On
Main swith ON
Turn Off
Main swith OFF
Parameters
Unit config
Compressor
0 sec
100 sec
20 sec
SDT (Compressor start delay)
CM2
5 min
2000
min
45 min
PDT (Pull down time)
CM3
180 min
2000
min
1440
min
CST (Cycle time)
CM4
24 hours
768
hours
160
hours
PLT (Endless purging max time)
VA5
Limits settings
0 bar
5 bar
0.5 bar
Comp Diff (Hysteresis min allowed ammonia pressure)
CM5
0 bar
12 bar
6.5 bar
Setpoint (Min allowed ammonia pressure)
CM1
Input/Output
Input / Output Display & Config