User Guide
|
Intelligent Purger System (IPS) for Ammonia - Technical data, installation, and use
10 |
BC297731816824en-000101 | 148R9643
Installation
The Danfoss IPS should be installed in
accordance with locations recommended in the
Connection locations and Connection points
sections .
The unit is intended for indoor installation only
in a non-ATEX atmosphere . The purger unit is not
explosion proof .
The purger unit should be kept in an upright
position all the way from receipt to final
installation .
Install the unit on a horizontal construction with
sufficient support allowing the purger subframe
to be boltet to the support . See example in fig 11 .
Maintain recommended distances in all
directions (fig . 11) to allow fan cooling and
service .
Allways leave the unit 12 hours from finished
installation before first time switching on
It is important that the support
construction is level to ensure the
internal liquid trap is properly filled .
Angle to horizontal < 2 degrees
Fig. 11
Fig. 12
300
500
500
750
750
780
459
60
385
6
Support construction
for 57 kg (126 lbs)
Purging pipe OD 17.2 for
rubber hose to water bath.
Do not unscrew restrictor
inside pipe
Welding
Enclosed weld flange
(see fig. 13)
Enclosed
gasket
Enclosed
bolts
Torque:
60 Nm (44.3 ft lb)
diagonal tension
354
176
4 x Ø11
25
300
27
A
271
544
Flange for ammonia connection (see fig. 13)
Purging pipe
OD 17.2 for
rubber hose to
water bath