manualshive.com logo in svg
background image

© Danfoss | DCS (MWA) | 2015.11 

DKRCI.PI.HL3.A1.02 | 520H10323 | 3

ENGLISH

Installation

Refrigerants

Applicable to HCFC, HFC and R717 (Ammonia). 

Flammable hydrocarbons are not recommended. 

The valve is only recommended for use in 

closed circuits. For further information please 

contact Danfoss. 

Temperature range 

–60/+120°C (–76/+248°F). 

Please note explicit limitations in function 

modules installation guides

Pressure range 

The valves are designed for a max. working 

pressure of 28 bar g (406 psi g).

Important:  

This pressure limitation is valid for all 

covered valves in this guide despite the 

function modules installation guides 

statement.

Applications 

All covered valves  can be used in suction, 

liquid, hotgas and liquid/vapor lines. 

The valves regulates the flow of the medium, 

modulating or on/off, depending on the actual 

configuration.

Regulating range 

Please refer to the regulating range of the 

enclosed specific function module installation 

guide

Design (fig. 7) 

For more details on ordered configuration 

please refer to the enclosed specific function 

module installation guide

Installation 

The valve must be installed with the spindle in 

vertically upwards position (fig. 1). 

The valve must be installed with the arrow 

in the direction of the flow and the top cover 

upwards. The top cover can be rotated 4 X 90° 

in relation to the valve body (fig. 2). 

Specific requirements for the individual 

configurations must be followed. See enclosed 

specific function module installation guide.  

Mounting of valve flanges 

•  Make sure that piping into which a valve/  

  flange is installed is properly supported and  

  aligned square and plumb to the joining 

 sections. 

•  Ensure that the finalized valve assembly is free  

  of any stresses from external loads. 

•  Make certain that the mating surfaces of   

  gasketed joints are free of rust and are in good

 condition. 

•  Use only new gaskets manufactured by 

 Danfoss. 

•  Make sure that the bolts are adequately 

  tightened in an alternating pattern. 

•  Ensure that flanges / valves are properly   

  pressure tested, leak tested, evacuated before  

  charging with refrigerant in accordance with  

  ANSI /IIAR 5, EN378-2 or ISO 5149-2. 

The enclosed valves must not be mounted in 

systems where the outlet side of the valve is 

open to atmosphere. The outlet side of the 

valve must always be connected to the system 

or properly capped off, for example with a 

welded-on end plate. 

Silver label

Inside the valve box you’ll find a small silver 

label with pressure information. Please place 

this label on the top cover. 

Tightening (fig. 6) 

Tighten the top cover, pilot and/or external 

connection with a torque wrench, to the values 

indicated in the table fig 6. 

Colours and identification 

The valves are Zinc-Chromated from factory. 

If further corrosion protection is required, the 

valves can be painted. 

Precise identification of the valve is made via 

the ID plate on the top cover. 

Protection of the ID plate when painting the 

valve is recommended. 

Maintenance 

Service 

The involved valves are easy to dismantle. 

Do not open the valve while the valve is still 

under pressure. 

Pressure relief can be done by carefully 

opening the manual operating spindle (not ICM 

versions). Small grooves along the thread will 

release refrigerant into open air. This operation 

must only be done after providing the correct 

countermeasures under local legislation. 

Dismantling of the individual function modules 

must be done according to fig. 3 and the more 

detailed descriptions in the function module 

installation guides. 

Assembly 

Remove any dirt from the body before the valve 

is assembled. Check that all channels in the 

valve are not blocked by particles or similar. 

If possible, apply some refrigeration oil to ease 

the insertion and to protect the o-rings. 

Tightening (fig. 6) 

Tighten the top cover and  externals with a 

torque wrench, to the values indicated in the 

table. 

ICM: Manual opening/closing of the 

motorized ICM valve is shown in fig. 4

ICS/ICLX:

Always pay attention to the spindle during 

operation of the manual opener (see fig 5a)

1.  Make sure that the C-clip (C) is positioned on  

  the spindle (B) and is intact. A new C-clip is  

  available in the inspection kit for the valve.

2.  Pay attention to the C-clip reaching the top  

  nut of the packing gland when turning the  

  manual stem clockwise.

  Never use excessive torque and stop

  turning when the C-clip gets in contact  

  with the top nut.

Manual opening/closing of the mechanical 

valves ICS/ICLX is shown in fig 5b.

Returning to normal operating mode:

ICLX: Turn the spindle clockwise until the C-clip 

gets in contact with the top nut.

ICS: Turn the spindle counterclockwise to the 

top point and continue turning until a torque of 

8 Nm (5.9 lb/ft) is reached.

Remount the cap and tighten it clockwise to 8 

Nm (5.9 lb/ft) torque.

Use only original Danfoss parts, including 

O-rings and gaskets for replacement. Materials 

of new parts are certified for the relevant 

refrigerant. In cases of doubt, please contact 

Danfoss. 

Drawings are only for illustration, not for 

dimensioning or construction. 

Danfoss accepts no responsibility for errors 

and omissions. Danfoss Industrial Refrigeration 

reserves the right to make changes to products 

and specifications without prior notice. 

Отзывы: