Installation Guide
Danfoss
Icon™
Master Controller 24 V
Reset or replace a
Danfoss
Icon™
Master Controller
24V
Factory resetting of Danfoss
Icon™
Master
Controller 24V
1 . Press
to select UNINSTALL
mode .
2 . On the
Danfoss
Icon
™
Master Controller 24V, press
and hold
and
for 3
seconds until the display says
.
3 . Press
OK
. All settings on
Master Controller are reset to
factory settings .
Note!
Individual room thermostats must be reset
locally, see chapter “Removing a thermostat”.
Replacing a defective Danfoss
Icon™
Master
Controller 24V
1 . Remove all thermostats and other units from
the system by following the procedure for
factory resetting .
2 . Make a note of how all wires are connected to
the
Danfoss
Icon
™
Master Controller 24V .
3 . Remove wiring to
Danfoss
Icon
™
Master
Controller 24V .
4 . Mount the new
Danfoss
Icon
™
Master Controller
24V and reconnect all wires to the same position
as on the replaced Master Controller .
5 . Set up system again as described in chapter
“Setting up the system” .
OK
Trouble shooting
If an error is detected, an alarm code will be displayed either on the
Danfoss
Icon
™
Master Controller
24V or on the thermostat .
Alarm code
Problem
Solution
Er03
You have set-up a cooling applica-
tion that requires a reference room
thermostat to be appointed .
Please go to the thermostat in the desired
reference room and enter the thermostat installer
menu . Set thermostat to
ON
in ME .6
”reference
room thermostat”
.
Er05
Communication lost to Radio
Module .
Please check that the cable is properly connected
in the Radio Module and
Danfoss
Icon
™
Master
Controller 24V .
Er06
Communication lost to room
thermostat .
Identify the room thermostat by looking at the
flashing outputs on the
Danfoss
Icon
™
Master
Controller 24V, or look at the thermostats . Wake
up thermostat, then press
on the thermostat .
Failing thermostat will say “NET ERR” .
Replace batteries on room thermostat and perform
a network test (activate NET TEST in menu on room
thermostat) .
Er07
Communication lost to Slave
Controller .
If wireless, check Radio Module connection to
Danfoss
Icon
™
Master Controller 24V . If wired
system, check the wire connecting the controllers .
Er08
Communication lost from Slave to
Master Controller .
If wireless, check Radio Module connection to
Danfoss
Icon
™
Master Controller 24V . If wired
system, check the wire connecting the controllers .
Er10
Communication lost to Repeater .
Check that the repeater is plugged into outlet / has
not been removed and outlet is
ON
.
Er11
Communication lost to Expansion
Module .
Check that Expansion Module is slidded fully into
place .
The potential free relay is activated on all Master
Controllers when heat is demanded on either
Master Controller .
SLA TYPA:
Pump is activated on
Danfoss
Icon
™
Master Controller 24V when heat is demanded on
either Master or Slave(s) .
SLA TYPB:
Pump relay is only activated on the
Danfoss
Icon
™
Controller 24V
to which the
thermostat with heat demand is assigned .
Slave type definition
10 | © Danfoss | FEC | 2019 .02
VIMCG30F | 088N3678
Содержание Icon Master
Страница 1: ...Installation Guide Danfoss Icon Master Controller 24 V www danfoss com ...
Страница 2: ......
Страница 104: ...24V 104 Danfoss FEC 2019 02 VIMCG30F 088N3678 ...
Страница 106: ... M 106 Danfoss FEC 2019 02 VIMCG30F 088N3678 ...
Страница 107: ...CN 088U1103 2 VIMCG30F 088N3678 107 Danfoss FEC 2019 02 ...
Страница 108: ...OK M 108 Danfoss FEC 2019 02 VIMCG30F 088N3678 ...
Страница 109: ...CN VIMCG30F 088N3678 109 Danfoss FEC 2019 02 ...
Страница 110: ...OK 110 Danfoss FEC 2019 02 VIMCG30F 088N3678 ...
Страница 111: ...CN OK VIMCG30F 088N3678 111 Danfoss FEC 2019 02 ...
Страница 112: ...112 Danfoss FEC 2019 02 VIMCG30F 088N3678 ...
Страница 113: ...CN VIMCG30F 088N3678 113 Danfoss FEC 2019 02 ...