ICM/ICAD Motorized Valve
Installation, Programming, and Troubleshooting
Danfoss (USCO / MKS), 11 - 006
DKRCI.EI.HT0.A1. / 50H1639
3
1. The ICM valve and ICAD motor actuator must be installed in horizontal pipelines with the
motor actuator pointing upwards.
. To prevent damage to O-rings and the valve seat, remove the one-piece ICM bonnet and
function module from the valve body prior to welding the valve body in the line. For ICM
0 (3/4” size) the valve seat is not integrated with the valve bonnet and must be
separately removed from the valve body with a 1 mm hex key prior to welding
(see diagrams below).
Removing ICM 5 to 65 bonnets
1) Remove the 4 bolts
) Rotate the bonnet as shown
3) Pry the bonnet out of the valve body
by using screw drivers between the
bonnet and valve body as shown
Installation
3
3
1
2c
3
2
3
No. Part description
1
ICM body (housing)
ICM bonnet/function module
a
O-ring for bonnet/function
module
b
O-ring for bonnet/function
module
c
O-ring for sealing ICAD motor
with ICM valve
3
ICM adapter/valve stem
4
ICM bonnet gasket
5
Bolts for ICM
11
ICAD motor actuator
1
O-ring for ICM 0 seat orifice
13
ICAD screws
14
Guide ring
15
ICM 0 valve seat orifice