Installation
Do not install ICAD before welding. This apply
for electrical as well as for mechanical installa-
tion. Please observe that ICAD when connected
to 24 V DC, will send out acoustic noise at stand
still. This has no influence on the function/
operation of the ICAD.
NOTE!
If media temperature is lower than
-30 °C (-22 °F) it is mandatory to set
parameter
¡30
and
¡31
.
See separate document attached in ICAD
box: document number AN285243155312
Use
ICAD 600A, ICAD 600A-TS and ICAD 1200A can
be used together with the following Danfoss
valves (fig. 1, 5a and 5b).
ICAD 600A
ICAD 600A-TS
ICAD 1200A
ICM 20
ICMTS 20
ICM 40
ICM 25
ICM 50
ICM 32
ICM 65
ICM 100
ICM 125
ICM 150
CVE pilot valve
Electrical data
Supply voltage is galvanically isolated from in-/
output.
Supply voltage
24 V DC (Tolerances; see below table)
Load
ICAD 600A, ICAD 600A-TS: 1.2 A
ICAD 1200A: 2.0 A
24 Volt DC ONLY
Please observe cable voltage drop.
Distance between the applied DC
transformer and the ICAD terminal
box may cause a voltage drop. Cross
section of cables and size of DC
transformer must be calculated so that
the voltage at all time
at the ICAD terminal
box*
, both during standstill and during
operation of ICAD, is within this range:
Prefabricated
ICAD cable length
Code number
1.5 m
027H0426
3 m
027H0438
10 m
027H0427
15 m
027H0435
Voltage ICAD terminal
(600A/1200A) [V DC]
Min.
21
22
23
24
Max.
26.4
* Do not measure inside the ICAD itself.
Fail safe supply
24 V DC (Tolerances; see table above)
Load
ICAD 600A, ICAD 600A-TS: 1.2 A
ICAD 1200A: 2.0 A
Anolog Input - Current or Voltage
Current
0/4 – 20 mA
Load: 200
W
Voltage
0/2 – 10 V DC
Load: 10 k
W
Analog Output
0/4 – 20 mA
Load: ≤ 250
W
Digital Input - Digital ON/OFF input by means of
voltfree contact (Signal/Telecom relays with gold-
plated contacts recommended) – Voltage input used
ON: Contact impedance < 50 W)
OFF: Contact impedance > 100 k
W
Digital Output - 3 pcs. NPN transistor output
External supply: 5 – 24 V DC (same supply as
for ICAD can be used, but
please note that the
galvanically isolated system
will then be spoiled).
Output load:
50
W
Load:
Max. 50 mA
Temperature range (ambient)
-30 °C/+50 °C (-22 °F/122 °F)
Enclosure
IP67 (~NEMA 6)
Electrical connection
Connection to ICAD is done via M12 connectors.
ICAD has two M12 male connectors build-in:
Power supply: 4 poled M12 male connector
Control signals: 8 poled M12 male connector
If ICAD is delivered with cables (1.5 m. (60 in.))
M12 female connectors: (Cable set with M12
female connectors in other lengths are available)
Power Supply cable with 4 poled M12
female connector
3 x 0.34 mm
2
(3 x ~22 AWG) (fig. 6)
I: Black
(+) 19 – 24 V DC fail safe
supply (optional).
II: White (+) 24 V DC
III: Brown (–) 24 V DC
Control cable with 8 poled M12
female connector
7 x 0.25 mm
2
(7 x ~24 AWG) (fig. 7)
A: Black
(–) Digital output.
Common Alarm.
B: Brown (–) Digital output.
ICM fully open.
C: Red
(–) Digital output.
ICM fully closed.
D: Orange (–) GND - Ground.
E: Yellow (+) Analog input
0/4 – 20 mA. *)
F: Green (+) Analog input 0/2 – 10 V /
DI1 - Digital ON/OFF
input.
G: Blue
(+) Analog output
0/4 – 20 mA. *)
*) If Neutral zone / 3 point control is
selected (parameter i02 = 3) then
E and G is used as DI2 - Digital
ON/OFF input. Se fig. 9.
Electrical installation
General procedure for ICAD 600A/ICAD
600A-TS/1200A installed on all ICM, ICMTS & CVE
valves.
All necessary electrical connections to be made.
ICM valve: Analog or digital operation
CVE/ICMTS valve: Analog only
Fig. 6
Analog operation
- 7 wired cable (A-G)
Modulation control. Valve to be controlled
from Danfoss electronics, type EKC/EKE (fig.
7), or third party electronics
(like e.g. PLC).
Connect analog input signals. Currrent
(mA) or Voltage (V). See
Parameter list
for
configuration of analog input signals.
Yellow (+) and Orange (GND) are used for
current (mA) input.
or
Green (+) and Orange (GND) are used for
Voltage (V) input.
Blue (+) and Orange (GND) are used
for current (mA) output (optional, not
mandatory).
Fig. 6
Digital operation
- 7 wired cable (A-G)
ON/OFF ICM solenoid valve operation. ICM
valve to be controlled by means of a digital
voltfree contact.
Connect digital input signals (fig. 8). See
Parameter list
for configuration of digital
input signals.
Green (+) and Orange (GND) are connected
to a voltfree contact.
Digital output signals are optional, not
mandatory.
Black (–) and Orange (GND) are connected
to auxiliary relay for Common Alarm.
Brown (–) and Orange (GND) are connected
to an auxiliary relay indicating ICM fully
open.
Red (–) and Orange (GND) are connected
to an auxiliary relay indicating ICM fully
closed.
Supply voltage
- 3 wired cable (I, II, III)
ICAD must be connected to a normal
24 V DC supply. As an option, a fail safe
supply is possible by means of a battery or
UPS (Uninterruptible Power Supply). When
voltage is applied as described below, ICAD is
ready to be configurated. See
Parameter list
.
ICAD configuration can be done
independently whether the ICAD is installed
on the valve or not.
See
Mechanical installation
.
Connect the White (+) and Brown (–) to a
24 V DC supply voltage (fig. 6).
Fail safe supply as an option (not mandatory).
Connect the Black (+) and Brown (–) to a fail
safe supply.
Mechanical installation
General procedure for ICAD 600A/ICAD
600A-TS/1200A installed on all valves (fig. 3).
Check that the three socket set screws are
fully unscrewed counter clockwise with a
2.5 mm Hexagon key.
Mount ICAD by slowly lowering it on top of
the valve.
The magnet coupling will drag the valve and
ICAD together and in position.
Push ICAD in place.
Fasten valve and ICAD with the three socket
set screws using a 2.5 mm Hexagon key.
Special moisture seal is damaged if
screws are removed (fig. 3, pos. A)
Neutral zone / 3 point control (fig. 9 - ICM only)
¡02
= 3
When
¡02
= 3 the factory setting of
¡04
(opening) and
¡14
(closing) are both set to 10.
When
¡02
= 3 the speed given by
¡04
(opening)
and
¡14
(closing) are active
¡13
(Inverse operation) is active
¡16
= 1 (Encoder operation enable) is active.
¡13
= 0 (Direct operation)
DI1 = DI2 = OFF
ICAD/ICM maintain current position
DI1 = DI2 = ON
ICAD/ICM maintain current position
DI1 = ON, DI2 = OFF
ICAD increase opening degree
DI1 = OFF, DI2 = ON
ICAD decrease opening degree
¡13
= 1 (Inverse operation)
DI1 = DI2 = OFF
ICAD maintain current position
DI1 = DI2=ON
ICAD maintain current position
DI1 = ON, DI2 = OFF
ICAD decrease opening degree
DI1 = OFF, DI2 = ON
ICAD increase opening degree