Application Guide | iC2-Micro Frequency Converters
Parameter
number:
2248
Unit:
s
Data type:
uint16
Access type:
Read/Write
P 5.12.7.10 Wake-Up Delay Time
Set the delay time for the motor to wait before waking up from sleep mode when the condition of waking up is met.
Default value:
0
Parameter type:
Range (0–3600)
Parameter
number:
2249
Unit:
s
Data type:
uint16
Access type:
Read/Write
7.6.12
Fieldbus Process Data (Menu Index 5.27)
P 5.27.1 PCD Write Selection
Use this parameter to select the parameters to be assigned to the PCD's telegrams. The number of available PCDs depends on the
telegram type. The values in the PCDs are then written to the selected parameters as data values.
Enter up to 16 different preset mapping 0–15 in this parameter, using array programming. If this parameter is active, addresses 2810–
2825 represent values of the 16 parameters. If this parameter is not active, addresses 2810 and 2811 are used as input-data-drive control
word and bus reference. Addresses 2812–2825 are reserved.
Default value:
0 [None]
Parameter type:
Selection
Parameter
number:
842
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter:
Selection number
Selection name
0
None
1
Minimum Reference
2
Maximum Reference
3
Ramp 1 Ramp Up Time
4
Ramp 1 Ramp Down Time
5
Ramp 2 Ramp Up Time
6
Ramp 2 Ramp Down Time
7
Jog Ramp Time
8
Quick Stop Time
9
Motor Speed Low Limit [Hz]
10
Motor Speed High Limit [Hz]
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |