Close ICM by turning the multi-function 

tool counter-clockwise, until it cannot be 

tightened further. 
Open ICM by turning the multi-function tool 

appox. 1 turn clockwise.

Install the ICAD actuator on the ICM adapter 

making sure it is pushed completely down. 

Fasten the set screws using a 2.5 mm hexagon 

key

Set screws

For ICAD already electrical connected 

to control system.

Program ICAD to manual mode.

(i01=2).

Install the ICAD actuator on the ICM 

adapter making sure it is pushed 

completely down. Fasten the set 

screws using a 2.5 mm hexagon key.

Program ICAD to calibrate to the 

actual ICM valve - i10 (password) 

and i26 (selection of ICM size).

Await calibration to finish.

Return ICAD to normal operation.

(i01=1)