2 | AN149686416719en-000401 © Danfoss A/S (MWA), 2021-01
Move down
to stop
Close ICM by turning the multi-function
tool counter-clockwise, until it cannot be
tightened further.
Open ICM by turning the multi-function tool
appox. 1 turn clockwise.
Install the ICAD actuator on the ICM adapter
making sure it is pushed completely down.
Fasten the set screws using a 2.5 mm hexagon
key
Set screws
For ICAD already electrical connected
to control system.
Program ICAD to manual mode.
(i01=2).
Install the ICAD actuator on the ICM
adapter making sure it is pushed
completely down. Fasten the set
screws using a 2.5 mm hexagon key.
Program ICAD to calibrate to the
actual ICM valve - i10 (password)
and i26 (selection of ICM size).
Await calibration to finish.
Return ICAD to normal operation.
(i01=1)