manualshive.com logo in svg
background image

MG.03.F5.02 - VLT is a registered Danfoss trademark

02/00

The control cables must be screened cables.

X101: Terminal block for analog/digital control signals

Terminal

Function

Example

No.

1

Analog input (0-20 mA)

Feedback

signal

2

Analog (0-10 V)/digital input 2

Speed

reference

3

Digital input (or pulse) 3

Reset

4

Digital input (or precise stop) 4

Start

5

Digital input (other) 5

Jog (fixed

speed)

6

24 V DC supply for digital inputs (max. 50 mA)

7

10 V DC supply for potentiometer (max. 15 mA)

8

0 V for terminals 1-7 and 9

9

Analog (0-20 mA)/digital output

Fault

indication

X100: Terminal block for data communication

Terminal

Function

No.

1

P  RS 485

for connection to

2

N  RS 485

bus or PC

3

5 V DC

Supply for RS 485 bus

4

0 V DC

T

T

T

T

Table B

able B

able B

able B

able B

Reset (pushbutton)

Start

Jog

Speed reference

Terminals

1: Analogue input

2: Analogue input

3: Digital input

4: Digital input

5: Digital input

6: 24 V DC supply

7: 10 V DC supply

8: 0 V

9: Output

-

Reset

 to be closed short time for

resetting fault trips

-

Start

 to be closed for changing

to 

run mode

-

Jog 

will run at fixed speed

while closed (10 Hz)

-

Speed reference

 (0-10 V)

determines speed while in 

run mode

Fig. 1

Fig. 1

Fig. 1

Fig. 1

Fig. 1

Factory setting

T

T

T

T

Table A

able A

able A

able A

able A

Fig. 2

Fig. 2

Fig. 2

Fig. 2

Fig. 2

175R0129

Mechanical installation

Mechanical installation

Mechanical installation

Mechanical installation

Mechanical installation
Install the FC motor with adequate access for routine
maintenance. Adequate space, particularly at the fan
inlet (50 mm), is necessary to facilitate airflow.

Where several FC motors are installed in close
proximity, care must be taken to ensure that there is
no recirculation of exhausted warm air.

N B !

N B !

N B !

N B !

N B !
Ambient temperature
To avoid the FC part getting overheated, the
ambient temperature is not to exceed 40 °C

and the 24-hour average temperature is not to exceed
35 °C. If the ambient temperature is in the range of
40 °C - 55 °C, a reduction of the service life of the FC
part is to be expected. For further information, please
see the section on derating in the Design Guide.

N B !

N B !

N B !

N B !

N B !
Bearings
Ball and roller bearings are despatched from
the works fully charged with grease. Shielded

bearings have sufficient grease for an operating life of
at least two years in normal ambient temperatures,
providing there is little or no leakage.

Tapping of fitments onto the motor shaft,
 with a hammer or mallet, causes bearing
damage. This results in increased bearing
noise and a significant reduction in bearing life.

VL

VL

VL

VL

VLT

T

T

T

T

®

®

®

®

®

 DriveMotor FCM 300 Quick Setup

 DriveMotor FCM 300 Quick Setup

 DriveMotor FCM 300 Quick Setup

 DriveMotor FCM 300 Quick Setup

 DriveMotor FCM 300 Quick Setup

Electrical connections

Electrical connections

Electrical connections

Electrical connections

Electrical connections
Remove the inverter box cover, which is held by four
screws, to obtain access to the terminals.

Remove the detachable terminal plugs from the
terminal blocks X100 and X101 to obtain access to
the mains terminals.

Lift only the corner of the black plastic cover by the
cable entries to expose the mains terminals L

1

, L

2

 and

L

3

 (see fig. 2).

N B !

N B !

N B !

N B !

N B !
Do not lift or remove the entire plastic
cover. The voltage on the FC motor is
dangerous and may lead to material

damage, serious injury or it may be fatal.

N B !

N B !

N B !

N B !

N B !
Mains terminals L

1,

 L

2

 and L

3

:

Make sure that your mains supply
corresponds to the voltage required by the FC
motor (see inverter label), TT and NT mains .

Connect the three mains phases to terminals L

1,

 L

2

 and

L

3

 and the earth to the separate terminal provided.

T

T

T

T

T ightening T

ightening T

ightening T

ightening T

ightening Tor

or

or

or

orques

ques

ques

ques

ques

L1, L2, L3

FCM  305-340

0,5-0,6 Nm

L1, L2, L3

FCM  355-375

1,2-1,5 Nm

Earth

 

ground FCM 305-375

3,4 Nm

Fixed wires:

Rated temperature for fixed wires min. 60

° 

C or

140

° 

F. Use copper conduction only.

N

N

N

N

N B !

B !

B !

B !

B !

You cannot change the rotation direction of the
motor by shifting around the phases. The
direction of rotation is clockwise by default.

Another direction of rotation can be programmed, see
the Design Guide.

Prefuses Max.

Prefuses Max.

Prefuses Max.

Prefuses Max.

Prefuses Max.

UL

1)

FCM 305-322

10A

FCM 330-340

15A

FCM 355-375

25A

IEC

1)

FCM 305-375

25A

1) 

Type gG prefuses must be used. If you want to maintain

UL/cUL you must use prefuses of the type Bussmann

KTS-R 500 V or Ferraz Shawmut, type ATMR (max. 30A). The

fuses must be placed for protection in a circuit that is capable of

supplying a maximum of 100,000 amps RMS (symmetrical), 500

V maximum.

Contr

Contr

Contr

Contr

Control terminals

ol terminals

ol terminals

ol terminals

ol terminals

For information on terminal blocks X100 and X101, please
see table A and B.

RS 485 switch

RS 485 switch

RS 485 switch

RS 485 switch

RS 485 switch
For terminating an RS 485 interface serial communication,
the bus must be terminated by a resistor network at both
ends. This is provided by setting both switches to ON.

LEDs

LEDs

LEDs

LEDs

LEDs
The FC motor has five LEDs which indicate the status of
the FC motor:

LED 300 (red):

Fault trip

LED 301 (yellow):

Warning

LED 302 (green):

Power on

LED 303-304 (green):

Communication

EMC-corr

EMC-corr

EMC-corr

EMC-corr

EMC-correct installation

ect installation

ect installation

ect installation

ect installation

The control cables must be screened cables to ensure
EMC-correct electrical installation.

Connect the screen to earth at both ends.

Avoid installation with twisted screen ends (pigtails), since
this ruins the screening effect at high frequencies. Use
cable clamps instead.

Start the FC motor

Start the FC motor

Start the FC motor

Start the FC motor

Start the FC motor
Connect mains. LED 302 (green) lights up to indicate
that the power is on. In Profibus versions, LED 303
will flash. For further information on Profibus, please
see the Profibus manual.

Connect terminal 4 and 6 to the start button (see fig.
1).

Connect terminal 2, 7 and 8 to the potentiometer
(see fig. 1).

The voltage on the FC motor is
dangerous when the motor is connected
to mains. Incorrect installation of the FC
motor may lead to material damage or

serious injury or it may be fatal.

Mount the inverter box cover.

Fastening torque: 2.2 - 2.4 Nm

Use the start button to start the FC motor and adjust the
speed by means of the potentiometer.

Motors type B14 & B34 mounting

1) Max length of the fixing bolts / screws

penetrating the B14 flange:

FCM 305-307 (frame 80) =

11.0 mm

FCM 311-315 (frame 90) =

11.5 mm

FCM 322-330 (frame 100) =

15.0 mm

FCM 340 (frame 112) =

15.5 mm

FCM 355-375 (frame 132) =

17.0 mm

2) The following precautions must be taken:

a) A non-setting jointing and sealing

compound must be used to seal the bolt /

screw threads in the motor flange.

b) A soft copper washer must be inserted

underneath the bolt / screw head.

c) The joint face between the motor flange

and the mounting must be sealed using

non-setting jointing and sealing compound.

For B34 types where it is only foot mounted, the flange

is not used. Then the bolts should be fitted in

accordance with parts a) & b) of item 2 to maintain the

IP55.

Отзывы: