3.14 Parameters: 13-** Smart Logic Control
3.14.1 Prog. Features
Smart Logic Control (SLC) is essentially a sequence of user-
defined actions (see
[x]) executed
by the SLC when the associated user-defined
event
[x]) is evaluated as TRUE by the
SLC .
The condition for an event can be a particular status or that
the output from a logic rule or a comparator operand
becomes TRUE. That will lead to an associated action as
illustrated:
Events and
actions
are each numbered and linked together
in pairs (states). This means that when
event
[0] is fulfilled
(attains the value TRUE),
action
[0] is executed. After this, the
conditions of
event
[1] will be evaluated and if evaluated
TRUE,
action
[1] will be executed and so on. Only one
event
will be evaluated at any time. If an
event
is evaluated as
FALSE, nothing happens (in the SLC) during the current scan
interval and no other
events
will be evaluated. This means
that when the SLC starts, it evaluates
event
[0] (and only
event
[0]) each scan interval. Only when
event
[0] is evaluated
TRUE, will the SLC execute
action
[0] and start evaluating
event
[1]. It is possible to program from 1 to 20
events
and
actions
.
When the last
event
/
action
has been executed, the
sequence starts over again from
event
[0] /
action
[0]. The
figure shows an example with three events/actions:
Starting and stopping the SLC:
Starting and stopping the SLC can be done by selecting .On
[1]. or .Off [0]. in
. The SLC always
starts in state 0 (where it evaluates
event
[0]). The SLC starts
when the Start Event (defined in
) is
evaluated as TRUE (provided that
On
[1] is selected in
). The SLC stops when the
Stop Event
(
) is TRUE.
resets all SLC
parameters and start programming from scratch.
3.14.2 13-0* SLC Settings
Use the SLC settings to activate, deactivate and reset the
Smart Logic Control sequence. The logic functions and
comparators are always running in the background, which
opens for separate control of digital inputs and outputs. .
13-00 SL Controller Mode
Option:
Function:
[0]
Off
Disables the Smart Logic Controller.
[1]
On
Enables the Smart Logic Controller.
13-01 Start Event
Option:
Function:
[0]
*
FALSE
Select the Boolean (TRUE or FALSE) input
to activate Smart Logic Control.
False
[0] enters the fixed value - FALSE
[1]
TRUE
True
[1] enters the fixed value - TRUE.
[2]
Running
Running
[2] The motor is running.
[3]
In range
In range
[3] The motor is running within
the programmed current and speed
ranges set in
to
[4]
On reference
On reference
[4] The motor is running on
reference.
Parameter Descriptions
FC 300 Programming Guide
3-106
MG.33.MA.22 - VLT
®
is a registered Danfoss trademark