the system.
START UP
With the balancing valve on the bypass fully open, operate the boiler until it reaches
it´s normal operating temperature. If hot water does not automatically flow to the
system then adjust (throttle) the bypass balancing valve until flow (hot water) to the
system is established. If flow is already to the system, no adjustment is required.
TEChNICAL DATA
Temperature Ranges:
Standard: Supply mounted 160°F/72°C
Return mounted 140°F/60°C
Return mounted 113°F/45°C
Type
Code No.
Size
Opening temp.
A
A/2
Cv
Weight
461 A 065 B 8920
1" NPT (Female x Female)
160°F/72°C
4.2
2.10
10.5
3.3 lb.
462 A 065 B 8921
1 ¼" NPT (Female x Female)
160°F/72°C
4.5
2.25
16.4
4.4 lb.
463 A 065 B 8922
1 ½" NPT (Female x Female)
160°F/72°C
4.7
2.35
20.0
5.3 lb.
464 A 065 B 8923
1" NPT (Female x Female)
140°F/60°C
4.2
2.10
10.5
3.3 lb.
465 A 065 B 8924
1 ¼" NPT (Female x Female)
140°F/60°C
4.5
2.25
16.4
4.4 lb.
466 A 065 B 8925
1 ½" NPT (Female x Female)
140°F/60°C
4.7
2.35
20.0
5.3 lb
464 AL 065 B 8917
1" NPT (Female x Female)
113°F/45°C
4.2
2.10
10.5
3.3 lb.
465 AL 065 B 8918
1 ¼" NPT (Female x Female)
113°F/45°C
4.5
2.25
16.4
4.4 lb.
466 AL 065 B 8919
1 ½" NPT (Female x Female)
113°F/45°C
4.7
2.35
20.0
5.3 lb
Max operating pressure:
85 psi/6 bar
Max operating temperature: 230°F (110°C)
Boiler
From system
or
mixing tank
1
3
2
To system
or
mixing tank