© Danfoss | DCS (ADAP-KOOL®) | 2018-11
DKRCE.PD.RL0.A3.02 | 3
Quick Start Guide, ERC 213
Parameter Name
Menu Code
Unit
Min. Value
Max. Value
Default Value
Value
Predefined applications
o61
–
–
–
App0
App0
Sensor type
o06
–
–
–
n10
n10
Temperature Setpoint
r00
°C
-100
200
2
2
Differential
r01
K
0.1
20
2
2.7
Min. set point limit
r02
°C
-100
200
-35
-35
Max. set point limit
r03
°C
-100
200
50
50
Display offset
r04
K
-10
10
0
0
Display Unit
r05
–
–
–
°C
°F
Calibration of Sair
r09
K
-20
20
0
0
Night Set back
r13
K
-50
50
0
0
Offset reference displacement
r40
°C
-50
20
0
0
Pull down duration
r96
min..
0
960
0
0
Pull down temp limit
r97
°C
-100
200
0
0
Alarm delay - Normal conditions
A03
min.
0
240
30
30
Alarm delay - pulldown / startup / def
A12
min.
0
240
60
60
High temp alarm
A13
°C
-100
200
8
8
Low temp alarm
A14
°C
-100
200
-30
-30
DI1 delay
A27
min.
0
240
30
30
DI2 delay
A28
min.
0
240
30
30
Condenser High temp alarm
A37
°C
0
200
80
80
Condenser High block limit
A54
°C
0
200
85
85
Voltage protection
A72
–
–
–
No
No
Min. cut-in voltage
A73
V
0
270
0
0
Min. cut-out voltage
A74
V
0
270
0
0
Max. voltage
A75
V
0
270
270
270
Defrost Method
d01
–
–
–
Electric
Electric
Defrost stop temperature
d02
°C
0
50
6
6.5
Defrost Interval
d03
hour
0
240
8
6
Max. defrost Time
d04
min.
0
480
30
30
Defrost delay at power up
d05
min.
0
240
0
0
Drip delay
d06
min.
0
60
0
0
Fan delay after defrost
d07
min.
0
60
0
0
Fan start temp after defrost
d08
°C
-50
0
-5
-5
Fan ON during defrost
d09
–
–
–
On
On
Defrost stop sensor
d10
–
–
–
None
None
Comp accumulated runtime
d18
hour
0
96
0
0
Defrost on demand
d19
K
0
20
20
20
Defrost delay after pulldown
d30
min.
0
960
0
0
Fan at compressor cutout
F01
–
–
–
FFC
FAo
Fan stop evaporator temp
F04
°C
-50
50
50
50
Fan ON time
F07
min.
0
15
2
2
Fan OFF time
F08
min.
0
15
2
2
Parameter sheet