Quick Start Guide, ERC 213

Parameter Name 

Menu Code 

Unit 

Min. Value 

Max. Value 

Default Value 

Value 

Predefined applications 

o61 

App0 

App0 

Sensor type 

o06 

n10 

n10 

Temperature Setpoint 

r00 

°C 

-100

200

2

2

Differential 

r01 

0.1

20

2

2.7

Min. set point limit 

r02 

°C 

-100

200

-35

-35

Max. set point limit 

r03 

°C 

-100

200

50

50

Display offset 

r04 

-10

10

0

0

Display Unit 

r05

 –

°C

°F 

Calibration of Sair 

r09 

-20

20

0

0

Night Set back 

r13 

-50

50

0

0

Offset reference displacement 

r40 

°C 

-50

20

0

0

Pull down duration 

r96 

min..

0

960

0

0

Pull down temp limit 

r97 

°C 

-100

200

0

0

Alarm delay - Normal conditions 

A03 

min. 

0

240

30

30

Alarm delay - pulldown / startup / def 

A12 

min. 

0

240

60

60

High temp alarm 

A13 

°C 

-100

200

8

8

Low temp alarm 

A14 

°C 

-100

200

-30

-30

DI1 delay 

A27 

min. 

0

240

30

30

DI2 delay 

A28 

min. 

0

240

30

30

Condenser High temp alarm 

A37 

°C 

0

200

80

80

Condenser High block limit 

A54 

°C 

0

200

85

85

Voltage protection 

A72 

No 

No 

Min. cut-in voltage 

A73 

0

270

0

0

Min. cut-out voltage 

A74 

0

270

0

0

Max. voltage 

A75 

0

270

270

270

Defrost Method 

d01 

Electric 

Electric 

Defrost stop temperature 

d02 

°C 

0

50

6

6.5

Defrost Interval 

d03 

hour 

0

240

8

6

Max. defrost Time 

d04 

min. 

0

480

30

30

Defrost delay at power up 

d05 

min. 

0

240

0

0

Drip delay 

d06 

min. 

0

60

0

0

Fan delay after defrost 

d07 

min. 

0

60

0

0

Fan start temp after defrost 

d08 

°C 

-50

0

-5

-5

Fan ON during defrost 

d09 

On 

On 

Defrost stop sensor 

d10 

None 

None 

Comp accumulated runtime 

d18 

hour 

0

96

0

0

Defrost on demand 

d19 

0

20

20

20

Defrost delay after pulldown 

d30 

min. 

0

960

0

0

Fan at compressor cutout 

F01 

FFC 

FAo 

Fan stop evaporator temp 

F04 

°C 

-50

50

50

50

Fan ON time 

F07 

min. 

0

15

2

2

Fan OFF time 

F08 

min. 

0

15

2

2

Parameter sheet

Содержание ERC 213

Страница 1: ...ress set to save Screen returns to main screen Quick Set up Control Application Code Application Defrost Type Defrost Termination Sensors Default Temp F r00 Temp Range min max F r02 r03 Default Dif F r01 Defrost Interval hrs d03 Max Defrost Time mins d04 Defrost Termination Temp F d02 AP0 Default No preset application full menu 2 36 31 22 4 6 30 43 AP1 Refrigeration Natural Time 1 39 36 43 4 4 30 ...

Страница 2: ... AC DO2 DO3 DO1 DO3 DO2 DO1 DO3 DO2 ERC 213 APP 1 ERC 213 APP 2 3 ERC 213 APP 4 5 Troubleshooting Power Supply Code Description Remedy applicable parameter code in parenthesis Common Alarm Error Codes A01 High temperature alarm Bring down temperature or increase high limit alarm limit A13 A02 Low temperature alarm Increase temperature or low temperature alarm limit A14 E27 Defrost sensor error Ver...

Страница 3: ...A14 C 100 200 30 30 DI1 delay A27 min 0 240 30 30 DI2 delay A28 min 0 240 30 30 Condenser High temp alarm A37 C 0 200 80 80 Condenser High block limit A54 C 0 200 85 85 Voltage protection A72 No No Min cut in voltage A73 V 0 270 0 0 Min cut out voltage A74 V 0 270 0 0 Max voltage A75 V 0 270 270 270 Defrost Method d01 Electric Electric Defrost stop temperature d02 C 0 50 6 6 5 Defrost Interval d03...

Страница 4: ...ty P74 no no Invert alarm relay P75 Normal Normal Keyboard lock P76 No No Main switch r12 Off On Controller status u00 S25 S20 Air temperature Sair u01 C 321 Present regulation reference u02 0 Evaporator temperature S5 u09 C 0 DI1 status u10 Off Off Night mode u13 Off Off DI2 status u37 Off Off Condenser temperature Sc U09 0 Compressor relay status u58 Off Off Fan relay status u59 Off On Defrost r...

Отзывы: