Compressor
Table 34: Compressor
Function
Code
Min.
Max.
Unit
AP0
AP1
AP2
AP3
AP4
AP5
AP6
AP7
Compressor
c--
Compressor minimum ON time
C01
0
30
min
0
0
0
0
0
0
0
0
Compressor minimum OFF time
C02
0
30
min
2
2
2
2
2
2
2
2
Compressor /Heater OFF delay at open door
C04
0
900
Secs
900
900
900
900
900
900
60
(1)
900
Zero crossing selection (YES / NO)
C70
no
YES
YES
YES
YES
YES
YES
YES
YES
YES
(1)
This option is a default setting in the controller and cannot be changed.
(1)
This option is a default setting in the controller and cannot be changed.
Others
Table 35: Others
Function
Code
Min.
Max.
Unit
AP0
AP1
AP2
AP3
AP4
AP5
AP6
AP7
Others
o--
Delay of outputs at startup
o01
0
600
sec
10
10
10
10
10
10
10
(1)
10
DI1 configuration
nC= Not configured; Sdc = Status display output,
doo = Door alarm with resumption, doA = Door
alarm without resumption, SCH = Main switch, nig
= Day/ Night mode, rFd = Reference displasement ,
EAL = External alarm, dEF = Defrost, Pud = Pull
down; Sc = Condensor Sensor
o02
nC
Sc
nC
nC
nC
nC
nC
nC
nC
nC
Serial address
o03
0
247
No
0
0
0
0
0
0
-
0.0
Password
o05
0
999
No
0
0
0
0
0
0
0
0
Sensor type selection (n5=NTC 5K, n10=NTC10K,
ptc=PTC, pt1=PT1000)
o06
(2)
n10
ptc
n10
n10
n10
n10
n10
n10
n10
n10
Cooling/Heating (rE=Cooling, Ht= Heating)
o07
rE
Ht
rE
rE
rE
rE
Ht
Display Resolution
o15
0.1
1.0
0.1
0.1
0.1
0.1
0.1
0.1
0.1
DO4 config (Lig=Light, ALA=Alarm)
o36
Lig
ALA
Lig
Lig
Lig
Lig
Lig
Lig
Lig
Lig
DI2 configuration
nC= Not configured; Sdc = Status display output,
doo = Door alarm with resumption, doA = Door
alarm without resumption, SCH = Main switch, nig
= Day/ Night mode, rFd = Reference displasement ,
EAL = External alarm, dEF = Defrost, Pud = Pull
down
o37
nC
Pud
nC
nC
nC
nC
nC
nC
nC
nC
Light Control
on= Always on, dAn = Day/Night, doo=Based on
door action
o38
on
doo
on
on
on
on
on
on
on
on
Predefined applications
o61
AP0
AP7
AP0
AP1
AP2
AP3
AP4
AP4
AP6
AP7
Save settings as factory
o67
no
YES
no
no
no
no
no
no
-
no
DO2 config (dEF=Defrost; ALA=alarm; Lig=Light)
o71
dEF
Lig
dEF
ALA
dEF
dEF
ALA
Display during defrost
o91
Air
-d-
-d-
-d-
-d-
-d-
-d-
-d-
-d-
-
(1)
This option is a default setting in the controller and cannot be changed.
(2)
This parameter can only be set when regulation is stopped, i.e. “r12” is set to 0
(1)
This option is a default setting in the controller and cannot be changed.
(2)
This parameter can only be set when regulation is stopped, i.e. “r12” is set to 0
Polarity
Table 36: Polarity
Function
Code
Min.
Max.
Unit
AP0
AP1
AP2
AP3
AP4
AP5
AP6
AP7
Polarity
P--
DI1 input polarity (nc/no)
no = normally open
nc = normally closed
P73
no
nc
no
no
no
no
no
no
no
no
DI2 input polarity (nc/no)
no = normally open
nc = normally closed
P74
no
nc
no
no
no
no
no
no
no
no
Invert alarm relay (0= normal, 1= invert relay ac-
tion)
P75
0
1
0
0
0
0
0
0
-
0.0
Key board lock (no / yes)(0=no, 1=yes)
P76
no
YES
no
no
no
no
no
no
-
no
© Danfoss | Climate Solutions | 2023.01
BC194286421698en-000901 | 29