Danfoss ERC 101 kit Скачать руководство пользователя страница 2

MAKING MODERN LIVING POSSIBLE

EN-Instruction sheet 

ERC 101 kit

Produced by Danfoss A/S (EL-MSSM/AZ) | March 2014

DKRCC.EI.RL0.A3.02/520H8599

2

Assignments

Assignments of inputs and outputs

S2 Application

S2A

Application to be controlled with Sensor 

C. (nC=Not Connected, Sco= Temp control, 

EuA= Evap temp, Con=Cond temp {condenser 

cleaning})

nC

Con -

nc

DO1 configuration

o1C Relay output 1. compressor (CoP) 

2. Heater HeT

CoP 

HeT

-

CoP

Password level1

PS1

Shop owner Most common parameters

0

999

-

0

Password level2

PS2

Service technician all parameters with read 

permission and possibility to change a 

number of parameters

0

999

-

0

Service

Service

Voltage value

uAC Current main power supply voltage

0

270

Vac

-

Relay 1 counter

rL1

Thousands of cycles of compressor relay since 

manufacture

0

999

1000

-

Interval counter  

int

Compressor run time since last defrost

0

999

min

-

Defrost time counter

dnt

Duration of last defrost cycle [min]

0

999

min

-

Firmware version

Fir

Danfoss software version number

-

-

-

-

Hardware version

HAr

Danfoss hardware version number

-

-

-

-

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifica-

tions already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Parameters

Problem solving

Menu

Parameters

Cod Description

Min

Max Unit

De-

fault

Setpoint

Stp

Setpoint

-50

80

C

2

Thermostat

tHE

Thermostat settings

Setpoint adjustment 

ratio

SPr

Current setpoint adjustment value diF * SPr

0.0

1.0

-

0.0

Differential

diF

Thermostat differential

0.0

20.0 K

2.0

Air temperature 

adjust

tAD

Air Temp Adjust

0.0

20.0 K

0

Alarm

ALA Alarm setting

High temperature 

alarm

HAt

Alarm is activated above this temperature 

(Celsius )

-50.0  80.0 C

15.0

Low temperature 

alarm

LAt

Alarm is activated below this temperature 

(Celsius )

-50.0  80.0 C

-50.0

Compressor

CoP Compressor Setting

Min run time

Crt

Minimum time compressor must run 0-30 

minutes

0

30

min

0

Min Stop time

CSt

Minimum time compressor must idle 0-30 

minutes

0

30

min

0

Max OFF time

Cot

Maximum time compressor must idle 0-480 

minutes

0

480

min

0

Error run time

Ert

Compressor run time if temperature sensor is 

not working (0-60 minutes )

0

60

min

0

Error stop time

ESt

Compressor stop time if temperature sensor is 

not working (0-60 minutes )

0

60

min

0

Minimum cut-in 

voltage

uLi

When compressor is OFF: 

lowest compressor start voltage (0-270 V)

0

270

Vac

0

Minimum cut-out 

voltage

uLo

When compressor is ON: 

lowest operation voltage (0-270 V)

0

270

Vac

0

Maximum voltage

uHi

When compressor is ON: 

highest operation voltage (0-270 V)

0

270

Vac

270

Power ON delay

Pod

Delay in seconds between power ON & 

compressor being activated

0

300

Sec

180

Defrost

dEF

Defrost Setting

Defrost type

dFt

No: defrost function is disabled, 

nat: OFF-cycle defrost (natural defrost)

no

nat

-

nat

Terminating temp

dtt

Temp at which defrost stop 

(evap temperature or cabinet temperature)

0

25

C

7

Def Min Interval

dii

The minimum time in hours between the start 

of each defrost cycle

0

96

hours 6

Def Max Interval

dAi

The maximum time in hours between the 

start of each defrost cycle

0

96

hours 7

Def Min time

dit

The minimum duration of a defrost cycle 

in minutes

0

240

min

10

Def Max time

dAt

The maximum duration of a defrost cycle 

in minutes

0

480

min

30

Condenser 

Protection

Con Condenser protection settings

Condenser Alarm 

Limit

CAL If condenser sensor exceeds this temperature, 

alarm is activated

0

85

C

75

Condens er Block 

Lim it

CbL

If this temperature is exceeded, compressor 

will be stopped

0

85

C

85

Condenser OK limit

CoL

Temperature at which compressor may start 

after a stop due to exceeding CbL

0

85

C

60

Condenser Low Temp

CLL

Temperature below which the compressor is 

not allowed to start

-50

20

C

-5

Display

diS

Display setting

Lock-time After 

defrost

dLt

Display lock time after defrost [0-60 min]

0

60

min

5

Problem

Probable cause

Remedy

Compressor does not start

Waiting for compressor delay timer

Check CoP->CSt

Line voltage to compressor too low or too high Check CoP->uLi, uLo, uHi

E01 or E02 is shown on display

E01: Sensor "S1" defective

Replace sensor

E02: Sensor "S2" defective

Display alternates between "Con" and 

temperature

Condenser temperature exceeds the 

temperature set in condenser settings menu

Clean condenser, 

Check Con->CAL, CbL

Display alternates between "Hi" and 

temperature

Temperature too high

Check ALA->HAt

Display alternates between "Lo" and 

temperature

Temperature too low

Check ALA-> LAt