EN-Instruction sheet 

ERC 101 kit

Produced by Danfoss A/S (EL-MSSM/AZ) | March 2014

DKRCC.EI.RL0.A3.02/520H8599

1

Technical highlights

Dimensions mm

Technical specifications

 

y

Pre-programmed - ready to use

 

y

Compressor protection against instable voltage

 

y

High condensing temperature protection

 

y

Compact design - total depth is only 46 mm

 

y

Real 16A power relay - up to 2.5 HP compressors

 

y

Automatically controlled brightness of large-size LED display

 

y

Fully compatible with flammable refrigerants (R290)

 

y

Moisture protection (housing & coating)

 

y

Advanced defrost algorithms

FEATURES

DESCRIPTION

Power supply

100 VAC - 240 VAC 50-60 Hertz, automatic switch mode 

power supply

Rated power

Less than 0.5 W

2 analogue inputs

Danfoss NTC Air temperature probes

Danfoss NTC Condenser

temperature probes (optional)

Output compressor 

relay

16 (16A) EN60730; 16 (16A) CQC;

16A (16A FLA/72A LRA) UL60730

Display

LED display, 3 digits, decimal point and 

multi functionality icons, °C scale

Operating 

conditions

0 °C to 55 °C, 93% rH

Storage conditions

-40 °C to 85 °C, 93% rH

Measurement range

-40 °C to 85 °C

Protection

Front: IP65/Rear: water and dust protection 

corresponds to IP31, accessibility of connectors limit 

rear part rating to IP00

Environmental

Pollution degree III 

(can be mounted inside a refrigerated cabinet), 

non-condensing

Resistance to heat 

& fire

Category D (UL94-V0)

EMC category

Category I

Operating cycles

Compressor relay: 

more than 175,000 at full load ((16A) 16A)

Approvals

R290/R600a: EN/IEC 60079-15:2005,

Glow wire according to EN/IEC 60335-1,

IEC/EN 60730, UL60730, NSF, CQC, GOST R 60730 

Note: These approvals are only valid when using the 

accessories listed in this document

^
^

78.25 mm

47.25 mm
51.25 mm

rear mounting

36.5 mm

28 mm

30 mm

71 mm

Input/output

DO1:

UL: 16FLA 72LRA,

IEC: 16(16)A

100-/-10% 50/60Hz
OT 55

DO
1(o1)

2

S1

S1

S2

S2

3

Input/

Sensors

Cabinet

Sensors

Evapor.

Sensors

Conden.

Sensors

DO & Input/Sensors

1   2   3

L

N

ERC 101

controller

Safety info

Risk of electrocution!

For mounting: do not connect mains power until the controller is correctly mounted.

For unmounting: disconnect the power supply before unmounting

Installation

Operation menu

 

y

Insert the ERC 101 in to the cabinet

 

y

Attach the clips to each side of the 

    ERC 101

Display/operation

Press BRIEFLY to defrost

Press UP/DOWN to

adjust setpoint

Flasching

Press any button to acknowlege

The green def symbol is list

when in defrost mode

Press  the button

5 seconds to ON/OFF

^
^

^
^

Press:

 

 

variable direct function defrost

Sub function:

 

BACK

Press:

 

 

tempearture setpoint

sub function:

 

UP

Press:

 

 

upper left button BACK 

to return to parameter group

Press and hold for 5 seconds

to enter the menu
Press: UP/DOWN to scroll

through the menu

To select: press the lower

left button (OK)

Press:

 

 

variable direct functionON/OFF

Sub function:

 

OK

Press:

 

 

tempearture setpoint

sub function:

 

DOWN

Press 5 sec both right buttons

to access the menu

1) Parameter groups

Higher left button to exit
Lower left button to confirm

Scroll through the

parameters group

Scroll through the

menu group

2) Parameter name

3) Parameter value

^

^

^

^

Higher left button to exit

Lower left button to confirm

^
^

 

IMPORTANT NOTE

The inputs are not galvanic separated and are connected directly to 

the mains supply! For that reason, door-switches, sensors as well as the cables must fulfil the reinforced 

insulation requirements.