Danfoss EKC 368 Скачать руководство пользователя страница 5

EKC 368 

Instructions  RI8JC353  ©  Danfoss  10/2009 

   5

English

Light-emitting diodes (LED) on front panel

There are LED’s on the front panel which will light up when the 
belonging relay is activated.
The three lowermost LED’s will flash, if there is an error in the 
regulation.
In this situation you can upload the error code on the display and 
cancel the alarm by giving the uppermost button a brief push.

Display

The values will be shown with three digits, and with a setting you 
can determine whether the temperature are to be shown in °C or 
in °F.

Operation

Menu survey

The buttons

When you want to change a setting, the two buttons will give you 
a higher or lower value depending on the button you are push-
ing. But before you change the value, you must have access to the 
menu. You obtain this by pushing the upper button for a couple 
of seconds - you will then enter the column with parameter codes. 
Find the parameter code you want to change and push the two 
buttons simultaneously. When you have changed the value, save 
the new value by once more pushing the two buttons simultane-
ously.

 

Gives access to the menu (or cutout an alarm)

 

Gives access to changes

 

Saves a change

Examples of operations

Set reference temperature
1. Push the two buttons simultaneously
2. Push one of the buttons and select the new value
3. Push both buttons again to conclude the setting
 
Set one of the other menus
1. Push the upper button until a parameter is shown
2. Push one of the buttons and find the parameter you want to 
change
3. Push both buttons simultaneously until the parameter value is 
shown
4. Push one of the buttons and select the new value
5. Push both buttons again to conclude the setting

Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep both buttons depressed at the same time as you reconnect the supply voltage

The controller can give the following messages:

E1

Error message

Errors in the controller

E6

Change battery in timer. Set the timer.

E7

Cut-out Sair

E8

Shortcircuited Sair

E12

Analog input signal is outside the range

A1

Alarm message

High-temperature alarm

A2

Low-temperature alarm

A43

Check supply voltage for the step engine

A44

Battery alarm (no voltage or too low voltage)

Function

Para-
meter

Min.

Max.

Fac. 
set-
ting

Normal display

Shows the temperature at the room sensor

-

°C

Give the lower button a brief push to see the 
temperature at the defrost sensor

-

°C

Reference

Set the required room temperature

-

-70°C 160°C

10

Temperature unit

r05

°C

°F

°C

External contribution to the reference

r06

-50 K

50 K

0

Correction of the signal from Sair

r09

-10,0 K 10,0 K

0

Correction of the signal from Sdef

r11

-10,0 K 10,0 K

0

Start/stop of refrigeration

r12

OFF

On

On

Alarm

Upper deviation (above the temperature setting)

A01

0

50 K

5

Lower deviation (below the temperature setting)

A02

0

50 K

5

Alarm’s time delay

A03

0

180 min 30

Monitoring of battery

A34

Off

On

Off

Defrost

Defrost method (ELECTRICITY/GAS)

d01

Off

GAS

Off

Defrost stop temperature

d02

0

25°C

6

Max. defrost duration

d04

0

180 min 45

Drip-off time

d06

0

20 min 0

Delay for fan start or defrost

d07

0

20 min 0

Fan start temperature

d08

-15°C 0°C

-5

Fan cut in during defrost (yes/no)

d09

no

yes

no

Delay for temperature alarm after defrost

d11

0

199 min 90

Regulating parameters

Actuator type:  1=KVS15,  2=KVS28-35, 3=KVS42-54  
4=User defined via AKM / For Danfoss only
Setting of menu only when r12 = off.

n03

1

4

1

P: Amplification factor Kp

n04

1

50

4

I: Integration time Tn (600 = off)

n05

60 s

600 s

120

D: Differentiation time Td (0 = off)

n06

0 s

60 s

0

Transient phenomenon
0: Fast cooling
1: Cooling with less underswing
2: Cooling where underswing is unwanted

n07

0

2

1

Start-up time after hotgas defrost

n08

0 min 20 min 1

Miscellaneous

Controller’s address

o03* 1

60

0

ON/OFF switch (service-pin message)

o04* -

-

Off

Define input signal of analog input
0: no signal 
1: 0 - 10 V
2: 2 - 10 V

o10

0

2

0

Set supply voltage frequency

o12

50 Hz 60 Hz

50

Service

Read temperature at the Sair sensor

u01

°C

Read regulation reference

u02

°C

Read value of external voltagt signal

u07

V

Read temperature at the Sdef sensor

u09

°C

Read status of input DI

u10

on/off

Read duration of defrost

u11

m

Opening degree of the valve

u23

%

*) This setting will only be possible if a data communication module has been 
installed in the controller.

SW =1.6x

Содержание EKC 368

Страница 1: ...RI8JC353 10 2009 084R9792 INSTRUCTIONS EKC 368 084R9792 Identification Sair Sdef Pt 1000 ohm 0 C AKS 11 Dimensions Principle IP 20 084B7079 ...

Страница 2: ...r English Dansk Principle Necessary connections Terminals 25 26 Supply voltage 24 V a c 18 19 Pt 1000 sensor at evaporator outlet 21 24 Supply to step motor 1 2 Switch function for start stop of regulation If a switch is not con nected terminals 1 and 2 must be shortcircuited 5 6 Battery the voltage will open the KVS valve if the controller loses its supply voltage Application dependent connection...

Страница 3: ...larme et si le régulateur est hors tension 8 9 Contact de relais pour marche arrêt du dégivrage 8 10 Relais marche arrêt du ventilateur 8 11 Contact de relais pour marche arrêt du refroidissement 16 17 Signal de courant d une autre régulation Ext Ref Si le signal de tension reçu provient d un automate PLC ou simi laire il faut que le module de transfert éventuel soit à isolation galvanique 18 20 S...

Страница 4: ...mperaturalarm A2 Lavtemperaturalarm A43 Kontrollér forsyningsspændingen til stepmotoren A44 Batterialarm ingen eller for lav spænding Funktion Para meter Min Max Fab indst Normalbillede Viser temperaturen ved rumføleren C Tryk kortvarigt på den nederste knap for at se temperaturen ved afrimningsføleren C Reference Indstil den ønskede rumtemperatur 70 C 160 C 10 Temperaturenhed r05 C F C Eksternt b...

Страница 5: ...g input signal is outside the range A1 Alarm message High temperature alarm A2 Low temperature alarm A43 Check supply voltage for the step engine A44 Battery alarm no voltage or too low voltage Function Para meter Min Max Fac set ting Normal display Shows the temperature at the room sensor C Give the lower button a brief push to see the temperature at the defrost sensor C Reference Set the require...

Страница 6: ...naloges Eingangssignal außerhalb des Bereichs A1 Alarmmitteilung Hoch Temperaturalarm A2 Tief Temperaturalarm A43 Kontrolle der Versorgungsspannung zum Stepmotor A44 Batteriealarm keine oder zu niedrige Spannung Funktion Para meter Min Max Werks einstel lung Normalbild Anzeige der Temperature am Raumfühler C Kurzzeitig die unterste Taste betätigen um die Temperatur beim Abtaufühler anzuzeigen C So...

Страница 7: ...ur A44 Alarme batterie tension trop basse ou défaillante Francais Function Para meter Min Max Reg usine Image normale Indique la température de la sonde d ambiance C Appuyer brièvement sur le bouton inférieur pour afficher la température de la sonde de dégivrage C Référence Régler la température ambiante désirée 70 C 160 C 10 Unités de température r05 C F C Supplément externe de la référence r06 5...

Страница 8: ...rvice Lectura de la temperatura del sensor Sair u01 C Lectura referencia de regulación u02 C Lectura de la señal de corriente externa u07 V Lectura de la temperatura del sensor Sdef u09 C Lectura del estado de entrada DI u10 on off Lectura de la duración del desescarche u11 m Grado de apertura de la válvula u23 Este ajuste será posible solo si se ha instalado una tarjeta de comunicación en el cont...

Отзывы: