Instructions  RI8BF552  ©  Danfoss  12/2005 

7

ENGLISH

Connection between the evaporating temperature and the 
actuator’s temperature (the values are approximate).

n01: The highest regulated room temperature will have a belonging t

o

 value which 

in turn indicates the value of the n01 setting. Due to tolerances in the actua-
tor, the setting value must be 10 K 

higher

 than shown in the curve.

n02: The lowest occurring suction pressure will have a belonging t

o

 value which in 

turn indicates the value of the n02 setting. Due to tolerances in the actuator, 
the setting value must be 10 K 

lower

 than shown in the curve.

CVQ

KVQ

CVMQ

n01 and n02

Start of controller

When the electric wires have been connected to the controller, 
the following points have to be attended to before the regulation 
starts:
1. Switch off the external ON/OFF switch that starts and stops the 

regulation.

2. Follow the menu survey, and set the various parameters to the 

required values.

3. Switch on the external ON/OFF switch, and regulation will start.

If the temperature fluctuates

When the refrigerating system has been made to work steadily, 
the controller’s factory-set control parameters should in most 
cases provide a stable and relatively fast regulating system.
If the system on the other hand oscillates, you must register the 
periods of oscillation and compare them with the set integration 
time T

n

, and then make a couple of adjustments in the indicated 

parameters.

If the time of oscillation is longer than the integration time:

(T

p

 > T

n

 , (T

n

 is, say, 4 minutes))

1. Increase T

n

 to 1.2 times T

p

2. Wait until the system is in balance again
3. If there is still oscillation, reduce K

p

 by, say, 20%

4. Wait until the system is in balance
5. If it continues to oscillate, repeat 3 and 4

If the time of oscillation is shorter than the integration time:

(T

p

 < T

n

 , (T

n

 is, say, 4 minutes))

1. Reduce K

p

 by, say, 20% of the scale reading

2. Wait until the system is in balance
3. If it continues to oscillate, repeat 1 and 2

4. If the system has been fitted with a thermostatic expansion 

valve, it must be set to minimum stable superheating. (If a 
specific T0 is required for the adjustment of the expansion valve, 
the two setting values for the actuator temperature (n01 and 
n02) can be set to the belonging value while the adjustment 
of the expansion valve is carried out. Remember to reset the 
values).

5. Follow the actual room temperature on the display. (On 

terminals 2 and 5 a current signal can be transmitted which 
represents the room temperature. Connect a data collection 
unit, if applicable, so that the temperature performance can be 
followed).

Содержание EKC 361

Страница 1: ...ICS or PM Princip Principle Montageprinzip Principe Mål Dimensions Maße Dimensions Instructions EKC 361 RI8BF452 RI8BF552 12 2005 Start stop ...

Страница 2: ...kationsmodul Det er vigtigt at installationen af datakommunikationsk ablet udføres korrekt Se separat litteratur nr RC8AC Tilslutninger Necessary connections Terminals 25 26 Supply voltage 24 V a c 17 18 Signal from actuator from NTC 23 24 Supply to actuator to PTC 20 21 Pt 1000 sensor at evaporator outlet 1 2 Switch function for start stop of regulation If a switch is not connected terminals 1 an...

Страница 3: ...llation des Daten kommunikationskabels korrekt vorgenommen wird Siehe separate Literatur Nr RC8AC Anschlüsse Raccordements nécessaires Bornes 25 26 Tension d alimentation 24 V c a 80 VA 17 18 Signal provenant de l actuateur de NTC 23 24 Tension vers l actuateur à PTC 20 21 Sonde Pt 1000 à la sortie de l évaporateur 1 2 Contact pour marche arrêt de la régulation Si aucun contact n est raccordé il f...

Страница 4: ...er Min Max Fab indstil Normalbillede Viser temperaturen ved den valgte føler Ved ICM ventil kan OD også vælges C Reference Indstil den ønskede rumtemperatur 70 C 160 C 10 C Temperaturenhed r05 C F C Indgangssignalets temperaturindflydelse r06 50 C 50 C 0 0 Korrektion af signalet fra Sair r09 10 0 C 10 0 C 0 0 Korrektion af signalet fra Saux r10 10 0 C 10 0 C 0 0 Start stop af kølingen r12 OFF 0 On ...

Страница 5: ...este tilfælde give et stabilt og relativt hurtigt reguleringssystem Hvis systemet derimod pendler skal du registrere pendlingernes periodetid og sammenligne den med den indstillede integrationstid Tn Og derefter foretage et par justeringer på de angivne parametre Hvis periodetiden er større end integrationtiden Tp Tn Tn er fx 4 minutter 1 Forøg Tn til 1 2 x Tp 2 Vent til anlægget igen er i balance...

Страница 6: ...e alarm Function Para meter Min Max Fac setting Normal display Shows the temperature at the selected sensor At ICM valve OD also can be selected C Reference Set the required room temperature 70 C 160 C 10 C Temperature unit r05 C F C Input signal s temperature influence r06 50 C 50 C 0 0 Correction of the signal from Sair r09 10 0 C 10 0 C 0 0 Correction of the signal from Saux r10 10 0 C 10 0 C 0 ...

Страница 7: ...stable and relatively fast regulating system If the system on the other hand oscillates you must register the periods of oscillation and compare them with the set integration time Tn and then make a couple of adjustments in the indicated parameters If the time of oscillation is longer than the integration time Tp Tn Tn is say 4 minutes 1 Increase Tn to 1 2 times Tp 2 Wait until the system is in ba...

Страница 8: ...Temperaturalarm A2 Tief Temperaturalarm Funktion Para meter Min Max Werks einstell Normalbild Anzeige der Temperature am gewählten Fühler Beim ICM Ventil kann OD auch gewählt werden C Referenz Einstellung der gewünschten Raumtemperatur 70 C 160 C 10 C Temperatureinheit r05 C F C Temperatureinfluss des Eingangssignals r06 50 C 50 C 0 0 Korrektur des Signals vom Sair r09 10 0 C 10 0 C 0 0 Korrektur d...

Страница 9: ...endeln sollte ist die Periodendauer der Pendelungen zu registrieren und mit der eingestellten Integra tionszeit Tn zu vergleichen Anschließend sind an den angege benen Parametern einige Justierungen vorzunehmen Bei einer Periodendauer größer als die Integrationszeit Tp Tn Tn ist z B 4 Minutten 1 Tn auf 1 2 x Tp erhöhen 2 Abwarten bis sich die Anlage wieder stabilisiert 3 Pendelt sie nach wie vor K...

Страница 10: ...rature de la sonde choisie Avec ICM ont peut également choisir OD C Référence Régler la température ambiante désirée 70 C 160 C 10 C Unités de température r05 C F C Influence sur la température du signal d entré r06 50 C 50 C 0 0 Correction du signal en provenance de Sair r09 10 0 C 10 0 C 0 0 Correction du signal en provenance de Saux r10 10 0 C 10 0 C 0 0 Arrêt marche du refroidissement r12 OFF O...

Страница 11: ...table et relativement rapide Par contre si le système oscille il faut enregistrer les périodes des oscillations et les comparer avec le temps d intégration réglé Tn Procéder ensuite aux ajustages des paramètres indiqués Si les périodes sont supérieures au temps d intégration Tp Tn Tn 4 minutes par exemple 1 Augmenter Tn à 1 2 x Tp 2 Attendre que l installation soit stable 3 S il y a encore des osc...

Страница 12: ...12 Instructions RI8BF552 Danfoss 12 2005 EKC 361 ...

Отзывы: