Manual RS8EB102 © Danfoss 09-2005 

5

Operation

Menu survey

Light-emitting diodes (LED) on front panel

There are LED’s on the front panel which will light up when the 

corresponding relay is activated.

The upper LED will indicate the valve’s opening degree. A short 

pulse indicates a slow liquid flow and a long pulse a fast liquid 
flow.

The three lowest LED’s will flash, if there is an error in the regula-

tion.

In this situation you can upload the error code on the display and 

cancel the alarm by giving the uppermost button a brief push.

Display

The values will be shown with three digits, and

 

after an opera-

tion the controller will return to its standard mode and show the 

measured discharge temperature.

The buttons

When you want to change a setting, the two buttons will give you 

a higher or lower value depending on the button you are push-

ing. But before you change the value, you must have access to the 

menu. You obtain this by pushing the upper button for a couple 

of seconds - you will then enter the column with parameter codes. 

Find the parameter code you want to change and push the two 

buttons simultaneously. When you have changed the value, save 

the new value by once more pushing the two buttons simultane-

ously.

 

Gives access to the menu (or cutout an alarm)

 

Gives access to changes

 

Saves a change

Examples of operations

Set reference

1. Push the two buttons simultaneously

2. Push one of the buttons and select the new value

3. Push both buttons again to conclude the setting

 

Set one of the other menus

1. Push the upper button until a parameter is shown

2. Push one of the buttons and find the parameter you want to 

change

3. Push both buttons simultaneously until the parameter value is 

shown

4. Push one of the buttons and select the new value

5. Push both buttons again to conclude the setting

SW = 1.1x

Function

Para-
meter

Min.

Max.

Fac.
setting

Normal display
Read the measured discharge gas temperature -

°C

If you wish to see the actual opening degree, 
give the lower button a brief push

-

%

If you wish to set the temperature reference 
you obtain access by pushing both buttons 
simultaneously

-

-70°C

160°C

125

Display / Control
Select unit (0=°C, 1=°F)

r05

0

1

0

Start / stop of regulation

r12

OFF

ON/on on

Alarm
Alarm limit

A16

-50°C

150°C

135

Time delay for alarm

A17

0 s

999 s

0

Function of the alarm relay when the tempera-
ture exceed the alarm limit 
0: Alarm relay active
1: Alarm relay not active

A19

0

1

1

Regulating parameters
Proportionale factor Kp

n04

0,5

30

15

I: Integration time Tn

n05

60 s

600 s / 
Off

120

Periode time

n13

3 s

10 s

3

Miscellaneous
Controller's address

o03*

0

119

-

ON/OFF switch (service-pin message)

o04*

OFF

ON

-

Set supply voltage frequency

o12

0/50 

Hz

1/60 

Hz

50

Select the showing of the "normal display":

0: Discharge gas temperature is shown
1: Valve’s opening degree is shown

o17

0

1

0

Manual control of outputs:
OFF:  No manual control
1: Valve output put in pos. ON
2: Alarm relay activated (cut out)

o18

OFF

2

off

Service
Read discharge gas temperature

u01

°C

Read temperature reference

u02

°C

Read status of input DI

u10

Read valve’s opening degree

u24

%

Error messages

The controller can give the following messages:

E1

Error message

Errors in the controller

E17

The temperature sensor is disconnected

E18

The temperature sensor is shortcircuited

A3

Alarm message

Alarm temperature limit is reached

*) This setting will only be possible if a data communication module has been 

installed in the controller.

Factory setting

If you need to return to the factory-set values, it can be done in this way:

- Cut out the supply voltage to the controller

- Keep both buttons depressed at the same time as you recon nect the supply voltage

Содержание EKC 319A

Страница 1: ...Temperature controller for limitation for the discharge gas temperature EKC 319A User Guide ADAP KOOL Refrigeration control systems...

Страница 2: ...ion valve type AKV or a type AKVA for NH3 is used The capacity requirement is determined by the size of the valve If the compressor is provided with a connection for liquid injection a pulse solenoid...

Страница 3: ...With setting 0 the alarm is also transmitted via the data communica tion With data communication the impor tance of the individual alarms can be defined Setting is carried out in the Alarm destinatio...

Страница 4: ...o18 Service Service A number of controller values can be printed for use in a service situation Read discharge gas temperature u01 Temperature Read the temperature reference u02 Temperature ref Read...

Страница 5: ...the buttons and select the new value 5 Push both buttons again to conclude the setting SW 1 1x Function Para meter Min Max Fac setting Normal display Read the measured discharge gas temperature C If...

Страница 6: ...brations Enclosure IP 20 Weight 300 g Montage DIN Rail Display LED 3 digits Terminals max 2 5 mm2 multicore Approvals EU Low Voltage Directive and EMC demands re CE marking complied with LVD tested ac...

Страница 7: ...e upload all the collected tempera ture values once a day Example of menu display Measurements are shown at one side and settings at the other You will also be able to see the parameter names of the f...

Страница 8: ...t such alternations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respecitve companies Danfoss and Danf...

Отзывы: