Manual  RS8CS302  ©  Danfoss  07-2005 

EKC 315A

Miscellaneous

Address

If the controller is built into a network with data communication, it must have an 

address, and the master gateway of the data communication must then know this 

address.

These settings can only be madewhen a data communication modulehas been 

mounted in the controller and the installation of the data communication cable has 

been completed.

This installation is mentioned in a separate document “RC8AC”

Following installation of a data com-

munication module, the controller can 

be operated on a par with the other 

controllers in ADAP-KOOL® refrigera-

tion controls.

The address is set between 0 and 119

o03

-

The address is sent to the gateway when the menu is set in pos. ON

(The setting will automatically change back to Off after a few seconds.)

o04

-

Valve and output signal

Define here the valve that is to regulate and the current signal to be transmitted to 

the analog output ”AO”. The current signal will show the superheat if o17=1. Or open-

ing degree of the valve, if O17=2. Or the S3 temperature if o17=3   0:Off

1: TQ valve and 0-20 mA

2: TQ valve and 4-20 mA

3: AKV valve and 0-20 mA

4: AKV valve and 4-20 mA

5: AKV valve and signal for an other controller. See appendix  3.

o09

AO type

Input signal for reference displacement

Definition of function and signal range.

0:  No signal

1:  Displacement of temperature reference with 0-20 mA

2:  Displacement of temperature reference with 4-20 mA

3:  Displacement of superheat reference with 0-20 mA

4:  Displacement of superheat reference with 4-20 mA

(4 or 0 mA will not give a displacement. 20 mA will displace the reference by the value 

set in menu r06)

o10

AI A type

Frequency

Set the net frequency.

o12

50 / 60 Hz

(50=0, 60=1)

Select signal for showing display

Here you can select the signal to be shown in the normal display.

The signal is also transmitted to the analog output. See O09.

1:  Superheat

2:  Valve’s opening degree

3:  Air temperature

(If you during operation give the lower button a brief push, you can see the follow-

ing: The S3 temperature, if 1 has been selected. The superheat reference, if 2 has been 

selected. Temperature reference if 3 has been selected).

o17

Display mode

Manual control of outputs

For service purposes the individual relay outputs and the AKV/A output can be forced 

into position ON. However only when regulation has been stopped.

OFF:  No override

1:  Relay to the solenoid valve is ON.

2:  AKV/A output is ON.

3:  Alarm relay is activated (connection established between terminals 29 and 31).

o18

-

Working range for pressure transmitter

Depending on the application a pressure transmitter with a given working range 

is used. This working range (say, -1 to 12 bar) must be set in the controller. The min. 

value is set.

o20

MinTrans Pres.

The max. value is set

o21

Max TransPres.

(Setting for the function o09)

Set the temperature value or opening degree of the valve where the output signal 

must be minimum

(0 or 4 mA)

o27

AO min. value

(Setting for the function o09)

Set the temperature value or opening degree of the valve where the output signal 

must be maximum (20 mA). (With a temperature range of 50 K (differential between 

the settings in o27 and o28) the dissolution will be better than 0.1 K. With 100 K the 

dissolution wil be better than 0.2 K.)

o28

AO max. value

Содержание EKC 315A

Страница 1: ...REFRIGERATION AND AIR CONDITIONING Controller for control of industrial evaporator EKC 315A Manual...

Страница 2: ...ctions Regulation of superheat Temperature control MOP function ON OFF input for start stop of regulation Input signal that can displace the superheat reference or the temperature reference Alarm if t...

Страница 3: ...valve will operate when refrigeration is required The relay for the alarm function works in such a way thatr the contact is cut in in alarm situations and when the con troller is de energised Modulati...

Страница 4: ...ensor cable r09 Adjust S2 Correction of signal from S3 Compensation possibility through long sensor cable r10 Adjust S3 Start stop of refrigeration With this setting refrigeration can be started and s...

Страница 5: ...is setting determines the valve s opening degree as a function of the change in evaporating pressure An increase of the evaporating pressure will result in a reduced opening degree When there is a dro...

Страница 6: ...with 4 20 mA 4 or 0 mA will not give a displacement 20 mA will displace the reference by the value set in menu r06 o10 AI A type Frequency Set the net frequency o12 50 60 Hz 50 0 60 1 Select signal f...

Страница 7: ...the thermostat or the duration of the last completed cutin u18 Ther RunTime Read the temperature at the S2 sensor u20 S2 temp Read superheat u21 SH Read the control s actual superheat reference u22 S...

Страница 8: ...Min Max Factory setting Normal display Shows the actual superheat valve s opening degree temperature De ne view in O17 K If you wish to see the expansion valve s actual opening degree give the lower b...

Страница 9: ...select ON 2 AKV A output select ON 3 Alarm relay activated cut out o18 o 3 O Working range for pressure transmitter min value o20 1 bar 60 bar 1 0 Working range for pressure transmitter max value o21...

Страница 10: ...084B7086 EKA 173 Data communication module accessories FTT 10 module 084B7092 EKA 175 Data communication module accessories RS 485 modul 084B7093 EKA 174 Data communication module accessories RS 485...

Страница 11: ...on line accumulators Your local Danfoss agent will be pleased to assist with further advice etc Appendix 1 Interaction between internal and external start stop functions and active functions Appendix...

Страница 12: ...be warmer when the valve is completely open If the value is high you can be sure that the valve is completely open but then it will also react slowly when it has to close again Appendix 6 The two typ...

Страница 13: ...lternatively it may be due to the fact that the set regulation parameters are not optimal If the time of oscillation is longer than the integration time Tp Tn Tn is say 240 seconds 1 Increase Tn to 1...

Страница 14: ...m the various menu displays The programme will for exam ple upload all the collected temperature values once a day Measurements are shown at one side and settings at the other You will also be able to...

Страница 15: ...EKC 315A Manual RS8CS302 Danfoss 07 2005 15...

Страница 16: ...s can be estab lished Danfoss can accept no responsibility for possible errors in catalogues brochures and other printed material Danfoss reserves the right to alter its products without notice This a...

Отзывы: