Manual 

Electronic superheat controller, type EKC 312

Function

Parameter Parameter by operation via data communication

Miscellaneous

Miscellaneous

Address

If the controller is built into a network with data communication, 

it must have an address, and the master gateway of the data 

communication must then know this address.

These settings can only be madewhen a data communication 

modulehas been mounted in the controller and the installation of 

the data communication cable has been completed.

This installation is mentioned in a separate document “RC8AC”.

Following installation of a data communication 
module, the controller can be operated on a par with 
the other controllers in ADAP-KOOL® refrigeration 
controls

The address is set between 1 and 60 (119)

o03

-

The address is sent to the gateway when the menu is set in pos. ON

(The setting will automatically change back to Off after a few 

seconds).

o04

-

Frequency

Set the net frequency.

o12

50/60 Hz
(50=0, 60=1)

Select signal for showing display

Here you can select the signal to be shown in the normal display.

The signal is also transmitted to the analog output. See o09.

1:  Superheat

2:  Valve’s opening degree

3:  Air temperature

(If you during operation give the lower button a brief push, you can 

see the following: The S4 temperature, if 1 has been selected. The 

superheat reference, if 2 has been selected. Temperature reference if 

3 has been selected).

o17

Display mode

Manual control of outputs

For service purposes the individual relay outputs and the 

ETS-output can be forced.

However only when regulation has been stopped.

OFF:  No override.

3: Alarm relay is activated (connection established between 

terminals 12 and 13).

After 600 seconds the manual control will be interrupted, and the 

setting will return to ”0”.

In settings 3, ”o45” will become active and the ETS output can be set 

manually.

o18

Manual ctrl

Manual control of the ETS valve

When ”o18” is activated the valve’s opening degre can be 

determined from this menu.

o45

Manual ETS OD%

Working range for pressure transmitter

Depending on the application a pressure transmitter with a given 

working range is used. This working range (say, -1 – 12 bar) must be 

set in the controller. The min. value is set.

o20

MinTransPres.

The max. value is set

o21

MaxTransPres.

Selection of control mode (loop Ctrl)

Depending on the application control can be carried out based on 

different parameters.

The two possibilities are shown in appendix 4.

1=normal control

2=double loop

The initial or factory setting for Loop Ctrl (o56) is 1, and factory 

settings for Kp factor (n04) is 3.0 and KpTo (n20) is 0.4.

When Loop Ctrl. is set for 2, Kp factor and KpTo will be initially set 

to 0.7 and 3.0 respectively. Changes can still be made to these 

parameters when Loop Ctrl is changed.

When Loop Ctrl is set to 1, Kp factor and KpTo are set to factory 

settings. 

Note, Loop Ctrl. can only be changed when Main Switch (r12) is off.

o56

Loop ctrl

Survey of functions

Содержание EKC 312

Страница 1: ...njection ensures optimum utilisation of the evaporator and hence a high suction pressure y y The superheating is regulated to the lowest possible value User manual Electronic superheat controller Type...

Страница 2: ...ve regulation of the refrigerant injection ensures optimum utilisation of the evaporator and hence a high suction pressure y y The superheating is regulated to the lowest possible value Functions y y...

Страница 3: ...on is stopped when the connection is interrupted The function must be used when the compressor is stopped The controller then closes the solenoid valve so that the evaporator is not charged with refri...

Страница 4: ...umption Controller ETS step motor 5 V A 1 3 V A Input signal Press transmitter 4 20 mA from AKS 33 Digital input from external contact func tion Sensor input 2 pcs Pt1000 ohm Alarm relay 1 pcs SPST AC...

Страница 5: ...ification factor Kp If the Kp value is reduced the regulation becomes slower n04 Kp factor I Integration time Tn If the Tn value is increased the regulation becomes slower n05 Tn sec Max value for the...

Страница 6: ...e if 2 has been selected Temperature reference if 3 has been selected o17 Display mode Manual control of outputs For service purposes the individual relay outputs and the ETS output can be forced Howe...

Страница 7: ...Te Read the temperature at the S4 sensor u27 S4 temp Read value of current signal from pressure transmitter AIB u29 AI B mA DO1 Alarm Read status of alarm relay For Danfoss only Start up time for safe...

Страница 8: ...ve s actual opening degree give the lower button a brief push 1s Define view in o17 Reference Units 0 C bar 1 F psig r05 0 1 0 Start stop of refrigeration r12 OFF On 1 Regulating parameters P Amplific...

Страница 9: ...tcircuited S2 sensor E17 Cut out S4 sensor E18 Shortcircuited S4 sensor E20 The input signal on terminals 14 15 is outside the range P0 signal A11 Alarm message No refrigerant has been selected A43 Ch...

Страница 10: ...are no substitute for normal good engineering practice Danfoss wil not be responsible for any goods or plant components damaged as a result of the above defects It is the installer s responsibility t...

Страница 11: ...the regulation 2 Follow the menu survey on page 6 and set the various para meters to the required values 3 Switch on the external switch and regulation will start 4 Follow the actual superheat on the...

Страница 12: ...uide for extended operation RC8AC Here you can see how a data communication connection to ADAP KOOL Refrigeration control systems can be established If the distance between EKC 312 and the ETS valve e...

Отзывы: