User Manual
7
Possible alarms during operation
Clogged drain
Description:
When clogged drain warning has been enabled, an alarm is raised when
the system constantly has been detecting moisture for 14 days .
If the EFIT™ 850 controls more than 1 system, and prioritizing
has been enabled, the time before clogged drain warning for the
down-prioritized system, can be much longer . The time is only
updated, when the system actually is allowed to heat the area
(e .g . the up-prioritized system is not heating)
Solution:
- Check gutter and down pipes for any obstacles preventing the melting
water to flow away .
- Check if sensors are covered with dirt .
Missing sensor
Description:
When the connection to a sensor is lost, the EFIT™ 850 alarms the user . At
the same time the EFIT™ 850 automatically switches the system to “Con-
stant Off” mode, and user interaction with the EFIT™ 850 is needed .
Solution:
- Acknowledge error and go to “Installer Site” in the menu system and
select “Change System” .
- Contact your local installer to get a replacement .
New sensor added
Description:
When a new sensor is added, the EFIT™ 850 alarms the user and at the
same time automatically switches to “Constant Off” mode . User interaction
is needed in order to correct the error .
Solution:
Acknowledge error and go to “Installer Site” in the menu system and select
“Change System” .
Sensor malfunction
Description:
When something is wrong with the readings from connected sensors to
the EFIT™ 850, an alarm is raised .
Not all error prone sensors can be discovered using this feature!
Solution:
- Acknowledge error and go to “Installer Site” in the menu system and
select “Change System” .
- Contact your local service centre to get a replacement .
S ystem
B
S ystem
A
A:Roof ˜
ÚStandby
B:Ground ¯ˆı
ÚMelting
Select system A:
Roof
Select system B:
Ground
View alarm
menu
5s
A:Roof ˜
B:Ground ¯ˆı
5s
View and set
operating mode
View sensor
measurements
View and set
operating mode
View sensor
measurements
Only visible when S ystem B is installed
!
A:Roof ˜
ÚStandby
B:Ground ¯ˆı
ÚMelting
Select system A:
Roof
Select system B:
Ground
View alarm
menu
5s
A:Roof ˜
B:Ground ¯ˆı
5s
Only vis ible when
S ys tem B is ins talled
!
S ys tem menu
(S ys tem A)
A:Roof ˜
B:Ground ¯ˆı
S ys tem menu
(S ys tem B)
Содержание EFIT 850
Страница 1: ...1 Installation and user manual EFIT 850 controller GB DAS ...
Страница 13: ...Installer Manual 13 B 230V 1 3 P 1 3 loads System A C 230V 1 3 P 1 3 loads System B EFIT 850 EFIT 850 ...
Страница 24: ...24 Sensor added If the user selected a new sensor to add the sensor is added Installer Manual ...
Страница 29: ...Appendix 29 Installer menu _ View statistics Change system Installer menu Appendix A ...
Страница 31: ...Appendix 31 View statistic View statistics Appendix A ...
Страница 36: ... C Article 088L8071 Version 01 01 ...