background image

L76

L76

V

I.K

M

.K

2.0

2

20

06

.12

V

I.K

M

.K

2.

02

20

06

.1

2

w

w

w

.d

an

fo

ss

.co

m

Use

r's G

uid

e

 

Installer's Guide

 

w

w

w

.d

an

fo

ss

.c

om

ECL C

om

for

t

In

sta

ller

's G

uid

e

ECL Comfort

User's Guide

*0

87

R8

17

7*

*V

IK

MK

20

2*

*087R8177*

*VIKMK202*

 

 

 

 

 

 

Hea

tin

g and D

HW con

tro

lle

r

Содержание ECL Comfort L76

Страница 1: ...K2 02 2006 12 VI KM K2 02 2006 12 www danfoss com User s Guide Installer s Guide www danfoss com ECL Comfort Installer s Guide ECL Comfort User s Guide 087R8177 VIKMK202 087R8177 VIKMK202 Heating and...

Страница 2: ...Safety Note To avoid injury of persons and damages to the device it is absolutely necessary to read and observe these instructions carefully Necessary assembly start up and maintenance work must be p...

Страница 3: ...e line A 18 Monitoring temperatures and system units line B 19 Manual control line B 20 Setting the heat curve line C 21 Heating cut out line 1 22 Flow temperature limits line 2 23 Room temperature in...

Страница 4: ...lated in the ECL controller based on the outdoor temperature S1 The lower the outdoor temperature the higher the desired ow temperature The motorized control valve M1 M2 in circuit 2 is opened gradual...

Страница 5: ...agram which has the best resemblance with your system and make your own combinations The functions can only be realized with ECL Comfort 301 and as of controller version 2 04 10 1 Indirectly connected...

Страница 6: ...d position the controller in the box Secure the controller with the xing screw Mounting on a DIN rail Mounting kit Order code No 087B1145 A mounting kit is necessary to mount the box with the controll...

Страница 7: ...supply voltage for M3 circuit III 9 P1 Circulation pump for circuit I heating 4 2 A 230 V a c 10 230 V a c supply for P1 11 P2 Circulation pump for circuit II heating 4 2 A 230 V a c 12 230 V a c sup...

Страница 8: ...r ESMU types Place the sensor so that it measures a representative temperature Slab temperature sensor ESMB 12 Place the sensor in the slab Valid for ESM 11 Do not move the sensor after it has been fa...

Страница 9: ...n be used for override purposes section 32 line 141 Connection example without ECA 9010 If the override switch has goldplated contacts you can choose one of the following solutions or a combination of...

Страница 10: ...everal controllers are installed in the system you can write a title on the ECL Card with a permanent ink pen Do not remove the ECL Card while copying The data on the ECL Card can be damaged When you...

Страница 11: ...sted Use the shift button to switch between the options The circuit selector shifts between circuit I and II You can adjust all settings and service parameters individually Update of the ECL Card afte...

Страница 12: ...1578 C 50 40 30 20 10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 Monitoring temperatures and system units line B 18 Shift to manual mode Controlled units 5 1 2 0 3 6 B 3 ON 1 ON 2 ON Contro...

Страница 13: ...e heat curve no matter if a room temperature sensor is connected or not Floor heating systems This controller is factory set for radiator systems which typically are high ow temperature systems To con...

Страница 14: ...for heating cut out Circuit Setting range Factory setting I II 10 30 C 18 18 C Set the outdoor temperature limit at which you want the heating system to stop The valve closes and after about 3 min th...

Страница 15: ...set to 40 The in uence at min limitation left corner of the display is set to 0 Heat curve H is 1 8 Result The desired ow temperature is changed by 2 x 40 x 1 8 x 0 1 14 4 degrees 23b B Reference roo...

Страница 16: ...Turning degrees x actuator speed sec degr Example 90 degrees x 2 180 sec Control parameters lines 4 7 circuit I II heating 26a 7 Neutral zone Nz Circuit Setting range Factory setting I 0 9 K 3 K Set...

Страница 17: ...table reaction to deviations A small integration constant will make the controller react fast but with less stability 6 Running time of the motorized control valve Circuit Setting range Factory settin...

Страница 18: ...close and that required pumps fans dampers and burners start and stop when operated manually See section 19 Having completed the manual operation check choose scheduled operation as controller mode C...

Страница 19: ...otorized control valve 5 250 sec 56 sec See section 26 7 Neutral zone Nz 0 9 K 3 K See section 26 ECL Card settings circuits II III 30b A Time and date Section 17 B System information Sections 18 19 C...

Страница 20: ...m function 1 99 min 10 min min 196 Service pin LON ON OFF OFF 197 LON reset ON OFF ON 198 Daylight saving time changeover ON OFF ON 199 Slave address 0 9 15 15 31b Service parameters 10 199 Circuit II...

Страница 21: ...ing time of the motorized control valve at DHW demand OFF 0 1 10 0 sec 1 6 sec sec 157 Acceptable temperature deviation below desired ow temperature T1ALARM OFF 1 30 K OFF 158 Acceptable temperature d...

Страница 22: ...personal settings turn the ECL Card over so that the yellow side faces you 10 Choice of room panel remote control Circuit Setting range Factory setting I II 1 8 5 5 Decides the communication with the...

Страница 23: ...erature 15 Adaptive function of room temperature Circuit Setting range Factory setting I II OFF 1 30 OFF OFF Controls how fast the room temperature adapts to the desired room temperature The adaptive...

Страница 24: ...ection 22 is overruled Desired ow temp C 10 C Time OFF No total stop Desired ow temp C 10 C Time 22 Pump exercise Circuit Setting range Factory setting I II ON OFF ON ON Exercises the pump to avoid bl...

Страница 25: ...it X axis Circuit Setting range Factory setting I II 30 15 C 15 15 C Set the outdoor temperature value see drawing Set the outdoor temperature value X coordinate for the lower limit The corresponding...

Страница 26: ...allel operation of DHW and heating circuits Circuit Setting range Factory setting I II OFF 1 99 K OFF OFF Choose whether the heating circuit is to operate in dependence of the DHW circuit OFF Independ...

Страница 27: ...erature for the anti bacteria function The DHW will be heated once a week at the set temperature to protect against bacteria at 00 00 on Mondays OFF The anti bacteria function is not active 1 100 The...

Страница 28: ...ure Connection example with ECA 9010 used if the override switch does not have gold plated contacts 16 Brown 15 Red Green S1 S6 The ECA 9010 module is powered by the system device bus which means that...

Страница 29: ...is active if the actual temperature rises above the acceptable deviation 30 C Flow temp T2ALARM line 148 Desired ow temp No alarm if the desired temp 30 C Outdoor temp The alarm signal can only be se...

Страница 30: ...temp 30 C Outdoor temp The alarm signal can only be sent via the module ECA 86 by means of relay R4 157 Acceptable temperature deviation below desired ow temperature T1ALARM Circuit Setting range Fac...

Страница 31: ...Setting range Factory setting II 1 250 K 200 K Set the proportional band A higher value will result in a stable but slow control of the ow temperature 1 250 Set the proportional band 185 Integration...

Страница 32: ...ng I 0 9 15 15 The setting is relevant when more controllers are working in the same ECL Comfort system connected via the system device bus ECL Comfort BUS 0 The slave receives information about the o...

Страница 33: ...ECL Card Do not remove the ECL Card while copying The data on the ECL Card can be damaged If you have copied your personal settings to the ECL Card you cannot restore the factory settings Copy persona...

Страница 34: ...circuit for heating the domestic hot water DHW 7b Humidity relative This value stated in refers to the indoor moisture content compared to the max moisture content The relative humidity is measured by...

Страница 35: ...is not too high See section 22 The temperature is unstable Check that the ow temperature sensor is correctly connected and in the right place Adjust the control parameters section 26 If the controlle...

Страница 36: ...ns to display line C section 1 further changes are not possible the controller continues its operation When the ECL Card is inserted with the yellow side facing you the controller can be operated agai...

Страница 37: ...ay Tuesday Sunday Circuit III Choose line C for the daily schedule Line Circuit Changeover time Periods with comfort temp are shown as black bars Time line Change the schedules Select appropriate day...

Страница 38: ...e desired mode section 2 During scheduled operation clock the state indicator a white arrow will show you the control mode of the selected circuit The white arrow will blink when this is a heating cir...

Страница 39: ...rrupted If the temperature value is displayed as the sensor in question is not connected means that the sensor is short circuited 1a Choose your favorite display circuit I Choose the display A B or C...

Страница 40: ...e two circuits Each line is shown in the display of the controller which gives you an instant overview of the operation settings etc How to use the ECL Comfort User s Guide This guide provides you wit...

Страница 41: ...for the ECL Comfort controller is composed of numbered sections Only sections that are relevant to your ECL Comfort controller are included here Installer s Guide Grey sections 10 and onwards Turn th...

Отзывы: