MENU > Settings > Flow temperature
Temp. min.
1x177
See Appendix “Parameter ID overview”
Set the min. duct / flow / inlet temperature for the system. The
desired duct / flow / inlet temperature will not be lower than this
setting. Adjust the factory setting, if required.
‘Temp. min.’ is overruled if 'Total stop' is active in Saving mode or
'Cut-out' is active.
‘Temp. min.’ can be overruled by the influence from the return
temperature limitation (see 'Priority').
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.
MENU > Settings > Flow temperature
Temp. max.
1x178
See Appendix “Parameter ID overview”
Set the max. flow / duct / inlet temperature for the system. The
desired temperature will not be higher than this setting. Adjust
the factory setting, if required.
The setting of ‘heat curve’ is possible for heating circuits only.
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.
VI.LG.H4.02
© Danfoss | 2017.05 | 67
Operating Guide ECL Comfort 210/296/310, application A230