Performance data
R32 50-60 Hz, Single compressor
Table 8: 50-60 Hz R32, Single compressor
Model
Nominal tons
60Hz
Nominal cooling capacity
Power input
COP
E.E.R.
TR
W
Btu/h
kW
W/W
Btu/h/W
50 Hz
DSF090
7.5
19958
68096
6.69
2.99
10.19
DSF100
8.5
21940
74860
7.13
3.08
10.50
DSF115
10
26349
89904
8.31
3.17
10.82
DSF130
11
29421
100384
9.19
3.20
10.93
DSF155
13
33772
115232
10.51
3.21
10.97
DSF175
15
39172
133655
12.07
3.24
11.07
DSF200
16.5
43329
147838
13.53
3.20
10.92
DSF270
22.5
59030
201416
17.98
3.28
11.20
DSF325
27
71480
243897
21.50
3.33
11.35
DSF485
40
107102
365443
31.67
3.38
11.54
DSF530
44
116998
399209
34.27
3.41
11.65
60 Hz
DSF090
7.5
26938
91911
8.68
3.10
10.59
DSF100
8.5
29362
100182
9.38
3.13
10.67
DSF115
10
34923
119157
10.79
3.24
11.04
DSF130
11
39465
134653
12.24
3.22
11.00
DSF155
13
45215
154273
13.82
3.27
11.16
DSF175
15
51618
176121
15.70
3.29
11.22
DSF200
16.5
57717
196932
17.63
3.27
11.17
DSF270
22.5
78270
267065
23.69
3.30
11.27
DSF325
27
95210
324866
28.54
3.34
11.38
DSF485
40
144600
493390
42.12
3.43
11.71
DSF530
44
156300
533311
45.6
3.43
11.70
NOTE:
TR
: Ton of Refrigeration,
COP
: Coefficient Of Performance
EER
: Energy Efficiency Ratio
Standard rating conditions for 50Hz: Evaporating temperature: 5°C (41°F), Condensing temperature: 50°C (122°F),
Superheat: 10K (18°F), Subcooling: 0K (0°F)
Standard rating conditions for 60Hz: Evaporating temperature: 7.2°C (45°F), Condensing temperature: 54.4°C (130°F),
Superheat: 11.1K (20°F), Subcooling: 8.3K (15°F)
Subject to modification without prior notification.
Data given for motor code 4 compressor with above conditions
For regular updates and detailed capacities, please refer to
.
Tandem and trio performances
The impact of manifolding on compressor performances depends widely of the customer system itself. Therefore, it
would be unrealistic to provide data that corresponds accurately to a particular system. In first approach, to support
compressors selection at full load, the manifold performances can be considered as the sum of capacities of the
compressors composing the manifold. For better accuracy, the customer should integrate the appropriate weighing
coefficients according to his system very pressure drops and part load levels.
© Danfoss | Climate Solutions | 2023.06
AB309735209512en-000603 | 13
Scroll compressors, DSF090 to DSF530 | Performance data