32
Installation
Guide
DLX series L00410622-01
CAUTION
The selected grid code must match the actual installation site; otherwise the
inverter may not operate or be compliant to relevant local and national
regulations due to incorrect limit values.
NOTICE
•
UK:
Follow the local electrical regulations when selecting the grid code; either
normal grid code setting or
UK 16A Limit
restricted grid code setting with a 16A
limitation for G83 compliance.
•
Germany:
Follow the local electrical regulations when selecting the grid code
setting; either
Germany 126
(VDE 0126-1-1) or
Germany 4105 (VDE-AR-N 4105)
.
The following screen is displayed while the settings are updated:
Grid Code Selection
NOTICE
An installation timer ensures that the grid settings can be changed (using the
Owner
password) within
5 hours
of feeding power to the grid. Thereafter it is only
accessible using the
Installer
password, which may only be obtained for installers
and grid operators by contacting
Danfoss
.
11
. Reactive Power Setting
Enter
– Call up the options
Select the actual reactive power setting:
1.
For installations <= 13.8 kVA:
V
DE 4105 0 – 13.8
2.
For installations > 13.8 kVA:
VDE 4105 13.8 –
Enter
– Confirm
Left
– Back
Right
– Next
Enter
– Confirm