background image

Cause

Troubleshooting

Remedy

11. Overfilled refrigerant cir-

cuit.

Using manometer apparatus and thermometer, check that

the unit’s overheating is correct for the specific refrigerant.

Follow the correct procedure (depending

on type of refrigerant) to add the correct

amount of refrigerant.

12. Changed conditions

Have you increased your

heating and/or hot water

demand?

If the heat pump has been dimensioned for a certain

demand and this demand is increased, the heat pump

might not be able to maintain the desired room tem-

perature.

If hot water consumption increases, a larger propor-

tion of time is used to produce hot water, which

means less time for heat production.

If the heat pump cannot cope with the de-

mand, replace it with one with a higher

output or supplement it with a higher out-

put auxiliary heater.

Problem – Auxiliary heater cuts in too soon

Cause

Troubleshooting

Remedy

1. The heat pump’s control

computer is not set/adjus-

ted to the customer’s re-

quirements/wishes.

Check the ROOM, CURVE, INTEGRAL A1 and INTEGRAL A2

settings

Adjust incorrect values in the heat pump’s

control computer. ROOM = Desired indoor

temperature CURVE = Should be set so that

the desired indoor temperature (ROOM) is

maintained regardless of the outdoor tem-

perature. INTEGRAL A1 = Start value for the

compressor. INTEGRAL A2 = Start value

(calculated from A1) for the auxiliary heater.

2. Changed conditions Have

you increased your heating

and/or hot water demand?

If the heat pump has been dimensioned for a certain

demand and this demand is increased, the heat pump

might not be able to maintain the desired room tem-

perature.

If hot water consumption increases, a larger propor-

tion of time is used to produce hot water, which

means less time for heat production.

If the heat pump cannot cope with the de-

mand, replace it with one with a higher

output or supplement it with a higher out-

put auxiliary heater.

3. Lack of refrigerant, not

enough refrigerant in the

system.

Using manometer apparatus and thermometer, check that

the unit’s overheating is correct for the specific refrigerant.

If there appears to be a leak in the refriger-

ant circuit, carry out leak tracing and any

necessary corrective action. If leak tracer is

not available, brush soap water on the sus-

pected leak and look for bubbles. Also

check for oil as this can come out from the

refrigerant circuit.

Problem – Short operating times despite heating demand

Cause

Troubleshooting

Remedy

ROOM and/or CURVE set too

high in combination with a

heating system with poor

circulation due to closed ra-

diator valves, too small ele-

ments or insufficient water

volume. A tight fitting sys-

tem with poor pipe dimen-

sions may produce the same

phenomena.

Check if the heat pumps starts, if the supply temperature

rises quickly whilst nothing happens to the return temper-

ature. If this happens and the heat pump is stopped by the

hysteresis function to later quickly drop in temperature

(supply) in order to start again, but cannot due to time

conditions in regulation, this means that the heat pump

cannot transport the heat away from the condenser as it

should. In such a case, hysteresis starts and stops the heat

pump often.

Adjust ROOM and CURVE if necessary. En-

sure that there is sufficient flow over the

condenser and the heating circuit.

Problem – Connection of external AH

Cause

Troubleshooting

Remedy

Incorrectly connected auxili-

ary heater. Does not start

when the control computer

gives the signal.

Check the connection against the instructions/wiring dia-

gram. Test the function in manual mode.

If the auxiliary heater is incorrectly connec-

ted, reconnect according to the instruc-

tions.

Service Instructions

DHP-AQ

VMGFJ202

Danfoss Heating Solutions

32

Содержание DHP-AQ Maxi

Страница 1: ...MAKING MODERN LIVING POSSIBLE Service Instructions DHP AQ www heating danfoss com...

Страница 2: ...anty if these instructions are not adhered to during installation or service The English language is used for the original instructions Other languages are a translation of the original instructions D...

Страница 3: ...mation Safety regulation 6 2 1 General safety precautions 6 2 2 Refrigerant 7 2 3 Electrical connection 8 2 4 Water quality 8 2 5 Commissioning 9 3 Troubleshooting 10 3 1 Alarm 10 3 2 Components 11 3...

Страница 4: ...lation Supplied with the heat pump on delivery The Service instructions and Wiring diagrams are available for download here www documentation heatpump danfoss com 1 2 Symbols in documents The instruct...

Страница 5: ...alve 304 Circulation pump 363 Exchange valve hot water 365 Supply line sensor 366 Return line sensor 406 or 62 Room sensor 408 EVU 417 Defrost sensor Explanation Component ordinary delivery according...

Страница 6: ...om a safety qualified person Caution The heat pump must be located in a frost free environment Caution The heat pump must be placed in an area with a floor drain Caution The heat pump must be located...

Страница 7: ...ied engineer Although the heat pump cooling system refrigerant circuit is filled with a chlorine free and environmentally approved refrigerant that will not affect the ozone layer work on this system...

Страница 8: ...by an authorized electrician and must follow applicable local and national regulations Caution The electrical installation must be carried out using permanently routed cables It must be possible to is...

Страница 9: ...culation pumps can be damaged Caution If the installation is only to be driven by the immersion heater during the installation ensure that the heating system is filled and the brine pump and compresso...

Страница 10: ...PPLY LINE SENSOR Sensor fault alternatively cable fault System supply line sensor RETURN LINE SENSOR Sensor fault alternatively cable fault Return line sensor HIGH RETURN LINE TEMP Return line tempera...

Страница 11: ...condarily with the auxiliary heater Hot water will stop to indicate that something noteworthy has occurred 3 2 Components 3 2 1 Outdoor unit 11 10 12 13 14 16 15 17 1 2 3 4 5 6 7 8 9 19 18 Fig 1 Compo...

Страница 12: ...5 DHP AQ Maxi 1 Control module transparent in image 2 Immersion heater 3 Reversing valve 4 Circulation pump 5 Water heater 3 3 Measurement points Caution When reading the resistance of the sensors the...

Страница 13: ...50 1194 8 5 55 7 1 60 1232 6 0 65 5 0 70 1271 4 2 75 3 7 80 3 1 85 2 7 3 3 1 Measurement checking sensors during fault tracing 1 Disconnect the relevant sensor from I O card terminal block 2 Measure t...

Страница 14: ...orth 7 SUPPLY LINE SENSOR 8 HOT WATER TOP 9 HOT WATER SENSOR RETURN LINE SENSOR Located on return pipe that runs to heat pump See sys tem solution in the Installation instructions 3 4 Check points Tem...

Страница 15: ...ist the most probable and common causes of the problem first When troubleshooting the cause of a problem start with the first cause and go down the list There may be more than one way of troubleshooti...

Страница 16: ...that the circulation pump is active in the control system s manual test menu Check if there is voltage to the circulation pump if there is and it does not run the circulation pump is jammed If this i...

Страница 17: ...be adjusted according to the system solution for large pressure drop 12 Blocked condenser on the water side If there is no strainer in the heating system there is a risk of dirt sticking in the conden...

Страница 18: ...place it If incorrectly set adjust to the correct value 6 Defective compressor Measurement check the voltage on the phase s each to zero at the compressor There must not be any large devi ation betwee...

Страница 19: ...5 No or insufficient circula tion in the heating system Check That the circulation pump spins That the shut off valves are open That the strainer is not blocked That there is no air in the heating sy...

Страница 20: ...e of the dis charge pipe 140 C 4 Lack of refrigerant not enough refrigerant in the system Using manometer apparatus and thermometer check that the unit s overheating is correct for the specific refrig...

Страница 21: ...e instruc tions Install flexible hoses according to the in structions 3 Installing suspending pipes Check if vibrations are transmitted via one of the pipe mountings in the installation Remove or move...

Страница 22: ...s Replace the compressor if the valve opens at too low pressure or when the compres sor is stationary Problem Noise miscellaneous Cause Troubleshooting Remedy 1 Vibrating protective sleeves on the pre...

Страница 23: ...n the service output Schrader valve 9 Insufficient exchange sur face to transfer the heat pump s output to the heat er Only applies to heat pumps with a separate heat er Is the exchange surface too sm...

Страница 24: ...electric heating element Use a buzzer and check if all coils in the electric heating el ement are intact If the electric heating element is defective replace it 6 The heat pump has stop ped on HIGH RE...

Страница 25: ...valves 11 The total output of the heat pump and auxiliary heater is too low in relation to the building s power de mand What is the building s power demand What is the output of the heat pump What is...

Страница 26: ...ve mo tor The motor should set the valve to the relevant posi tion depending on operat ing conditions If it does not hot water from the water heater will mix with the radi ator water Check the functio...

Страница 27: ...ess of the outdoor tempera ture CURVE5 0 5 The supply temperature can be adjusted up or down 5 C at these out door temperatures HEAT STOP Stops all production of heat when the outdoor temperature is t...

Страница 28: ...If AUX HEATER mode is selected and you no longer want it change to AUTO the heat pump then controls both the com pressor and auxiliary heater 2 The compressor cannot run due to an alarm Check the ala...

Страница 29: ...put auxiliary heater Problem The auxiliary heater is in operation but not the compressor Cause Troubleshooting Remedy 1 Operating mode AUX HEATER is selected If this operating mode is selected the au...

Страница 30: ...e temperature by feeling the pressure pipe If the phases are correctly sequenced it should be hot not just warm even a distance from the compressor When the compressor runs with the phases incorrect l...

Страница 31: ...he phases are in the incorrect order switch two incoming phases at the main terminal block and recheck according to the troubleshooting window 8 The compressor has been stopped by the operating pressu...

Страница 32: ...the heat pump cannot cope with the de mand replace it with one with a higher output or supplement it with a higher out put auxiliary heater 3 Lack of refrigerant not enough refrigerant in the system U...

Страница 33: ...d that it is correctly calibrated Calibrate if necessary Problem Build up of ice under and around the outdoor unit Cause Troubleshooting Remedy Insufficient drainage Does a lot of ice accumulate under...

Страница 34: ...Service Instructions DHP AQ VMGFJ202 Danfoss Heating Solutions 34...

Страница 35: ...Service Instructions DHP AQ Danfoss Heating Solutions VMGFJ202 35...

Страница 36: ...rves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifica...

Отзывы: