![Danfoss DGS Скачать руководство пользователя страница 5](http://html.mh-extra.com/html/danfoss/dgs/dgs_installation-manual_506483005.webp)
© Danfoss | DCS (ADAP-KOOL®) | 2018.12
RI8SP202 | 5
Menu Survey
Function
Min
Max
Factory
Unit
AKM name
Gas level
Sensor 1 Actual gas level in % of range
0.0
100.0
-
%
Gas level %
Sensor 1 Actual gas level in ppm
0
FS
2
-
ppm
Gas level ppm
Sensor 2 Actual gas level in % of range
0.0
100.0
-
%
2: Gas level %
Sensor 2 Actual gas level in ppm
0
FS
2
-
ppm
2: Gas level ppm
Alarms
Alarm settings
Indication of critical alarm (critical alarm of Gas1 or Gas2 active)
0: No active alarm(s)
1: Alarm(s) active
0
1
0
-
GD alarm
Common indication of both critical and warning alarm as well as
internal and maintenance alarms
0: No active alarm(s), warning(s) or errors
1: Alarm(s) or warning(s)) active
0
1
0
-
Common errors
Gas 1 Alarm limit in %.
Alarm limit in % (0-100), not lower 1: Warn Limit allowed
0.0
100.0
HFC: 25
CO2: 25
R290: 16
%
Crit. limit %
Gas 1 Alarm limit in ppm
Alarm limit in ppm; 0: Warning Signal deactivated
0
FS
2
HFC: 500
CO2: 5000
R290: 800
ppm
Crit. limit ppm
Gas 1. Warning limit in % (0-100)
0
100.0
HFC: 25
CO2: 25
R290: 16
%
Warn. limit %
Gas 1
Warning limit ppm 0: Warning Signal deactivated
0.0
FS
2
HFC: 500
CO2: 5000
R290: 800
ppm
Warn. limit ppm
High (critical and warning) alarm delay in seconds, if set to 0: no delay 0
600
0
sec
Alarm delay s
When set to 1, the audible sounder are reset (and the relays if
defined: Relay rest enable) to no alarm indication. When the alarm is
reset or the time out duration is exceeded, the value is reset to 0.
Note: The alarm condition is not reset only the output indication is
reset.
0: Alarm outputs not reset
1: Alarm outputs reset –buzzer muted and relays reset if configured
0
1
0
-
Reset alarm
Duration of alarm reset before automatic re-enable of alarm outputs.
A setting of 0 disables the ability to reset alarm.
0
9999
300
sec
Reset alarm time
1
Relay reset enable:
Relay reset with alarm acknowledge function
1= (default) Relays wil be reset if the alarm acknowledge function is
activated
0: Relays remains active until the alarm condition clears
0
1
1
-
Relay rst enable
1
Gas 2 Alarm limit in %.
Alarm limit in % (0-100), not lower 1: Warn Limit allowed
0.0
100.0
CO2: 25
%
2:Crit. limit %
Gas 2 Alarm limit in ppm
Alarm limit in ppm; 0: Warning Signal deactivated
0
FS
2
CO2: 5000 ppm
2:Crit. limit ppm
Gas 2. Warning limit in % (0-100)
0
100.0
CO2: 25
%
2:Warn. limit %
Gas 2. Warning limit ppm 0: Warning Signal deactivated
0.0
FS
2
CO2: 5000 ppm
2:Warn. limit ppm
High (critical and warning) alarm delay in seconds, if set to 0: no delay 0
600
0
sec
2:Alarm delay s
Service
Status of the sensors warm up period
0:Ready
1: Warming Up 1 or more sensors
0
1
0
-
DGS Warm-up
SW 1.1x