DEVIreg™ Smart
Installation Guide
8
4
Mounting Instructions
Please observe the following placement guidelines:
Place the thermostat at a suitable height on the wall
(typically 80-170 cm.). Switch can be placed on free
area on the wall.
The thermostat/switch should not be placed in wet
rooms. Thermostat/switch must be placed outside
zone 2. Place it in an adjacent room and use floor
sensor only. Always place the thermostat/switch
according to local regulation on IP classes.
Do not place the thermostat on the inner side of a
poorly insulated exterior wall.
Always install the thermostat at least 50 cm from
windows and doors, due to draft, when using regu-
lation in: floor and room mode or room alone mode.
Do not place the thermostat in a way that it will be
exposed to direct sunlight.
Содержание DEVIreg Smart
Страница 25: ...DEVIreg Smart 25 Installation Guide 10 Disposal Instruction ...
Страница 26: ...DEVIreg Smart Installation Guide 26 ...
Страница 27: ...DEVIreg Smart 27 Installation Guide ...