EN
Ready-making of the cold tail
Drawing
Designation
Tools
50
- Outer sheath removed
Remove 50 mm of the outer sheath
Knife and wire
cutter
50
Brown
Blue
Yellow/Green
- Primary insulation removed
Remove the outermost 50 mm of the
secondary insulation too.
Knife and wire
cutter
10
Brown
Blue
Yellow/Green
- Wire insulation removed
Strip off approx. 10 mm of each of
the three conductors. Provided two
conductor cold tail with screen is used,
the screen is released and twisted.
Wire cutter
Assembly process
Drawing
Designation
Tools
Brown
Blue
Yellow/Green
- Rivets added and squeezed
Now the two cables are ready for assembly.
On the cold lead 1,0 mm² rivets are squeezed
with an appropriate pliers onto the two
conductors and 1,0 mm² are squeezed onto
the ground wire (yellow/green).
Crimping pliers
Brown
Blue
Yellow/Green
150
- Heat shrink tube (Length =
150 mm) put over the cold lead
Now, put the 19/5 heat shrink tube
(length = 150) over the outer sheath of the
cold tail.
45
Yellow/Green
- Heat shrink tube (length =
45 mm) put over the conductors
Now, put the two 4/1 heat shrink tube
(length = 45 mm) over the two conductors
(L (Brown) + N (Blue)) of the cold tail with
the squeezed 1,0 mm² rivets.
85
- Heat shrink tube put over
the heating cable
Now, put the 9/3 heat shrink tube (Length
85 mm) over the outer sheath of the
heating cable. Be aware in this process that
the twisted and released aluminum foil
screen do not provide any damages to the
heat shrink tube.
Installation Guide Connection kit - cable to cold lead + end termination (Pipeheat)
DEVI
10
Содержание DEVI 140F0955
Страница 2: ......
Страница 59: ...Installation Guide Connection kit cable to cold lead end termination Pipeheat 59 DEVI...