Installation
Maximum inclination from the vertical plane while operating must not exceed 3 degrees.
Mounting
Compressor mounting
Compressor holding
charge
Each compressor is shipped with a nominal dry
nitrogen holding charge between 0.3 and 0.7 bar
and is sealed with elastomer plugs.
Before the suction and discharge plugs are
removed, the nitrogen holding charge must be
released via the suction schrader valve to avoid
an oil mist blowout. Remove the suction plug
first and the discharge plug afterwards. The plugs
shall be removed only just before connecting the
compressor to the installation in order to avoid
moisture from entering the compressor. When
the plugs are removed, it is essential to keep the
compressor in an upright position so as to avoid
oil spillage.
Compressors CH290 & 485 dedicated for
parallel (versions AA and AB) mounting come
delivered with rigid mounting spacers for parallel
mounting.
CH290 used in single applications, are delivered
with flexible grommets. The grommets must
be compressed until contact between the
flat washer and the steel mounting sleeve is
established. The grommets attenuate to a great
extent the transmission of compressor vibrations
to the base frame.
The required bolt size for the CH290 & 485
compressors is HM8-55. This bolt must be
tightened to a torque of 21 Nm.
Manifoldable compressor
with rigid spacers
Single compressor
with rubber grommets
HM 8 bolt
Lock washer
Flat washer
Steel mounting sleeve
Rubber grommet
Nut
27.5 mm
Compressor
base plate
HM 8 bolt
Lock washer
Flat washer
Rigid spacer
Nut
Nut
29.5 mm
34
FRCC.PC.026.A4.02
Application Guidelines