14
Installation Guide
CCR2
SMT/SI
VI.D1.E2.1R
Heating Solutions
13. Temperature set in the circulation risers and disinfection time:
Temperature
of disinfection
[ °C]
Time setting for thermal disinfection
in: hour … Minute …
Minimum
required
Maximum
recommended
50
6 h 20 minute
7 h 30minute
51
6 h 10 minute
7 h 20 minute
52
4 h 00 minute
5 h 50 minute
53
2 h 00 minute
4 h 00 minute
54
1 h 00 minute
2 h 00 minute
55
0 h 50 minute
2 h 00 minute
56
0 h 40 minute
1 h 20 minute
57
0 h 20 minute
1 h 00 minute
58
0 h 15 minute
0 h 50 minute
59
0 h 15 minute
0 h 45 minute
60
0 h 14 minute
0 h 40 minute
61
0 h 13 minute
0 h 35 minute
62
0 h 12 minute
0 h 30 minute
63
0 h 12 minute
0 h 28 minute
64
0 h 11 minute
0 h 27 minute
65
0 h 11 minute
0 h 26 minute
Temperature
of disinfection
[ °C]
Time setting for thermal disinfection
in: hour … Minute …
Minimum
required
Maximum
recommended
66
0 h 10 minute
0 h 25 minute
67
0 h 9 minute
0 h 25 minute
68
0 h 8 minute
0 h 22 minute
69
0 h 7 minute
0 h 21 minute
70
0 h 6 minute
0 h 20 minute
71
0 h 6 minute
0 h 18 minute
72
0 h 6 minute
0 h 14 minute
73
0 h 5 minute
0 h 12 minute
74
0 h 4 minute
0 h 10 minute
75
0 h 3 minute
0 h 10 minute
76
0 h 3 minute
0 h 10 minute
77
0 h 2 minute
0 h 9 minute
78
0 h 2 minute
0 h 8 minute
79
0 h 2 minute
0 h 6 minute
80
0 h 2 minute
0 h 6 minute
CCR2 ModBus protocol details
Data type : Coil [bool]
Coil No.
Description
MB_CoilOut [0]
- disinfection permitted
MB_CoilOut [1]
- disinfection in progress
MB_CoilOut [2 … 9]
- open valves ( 0 … 7)
MB_CoilOut [10 … 17]
- risers with open valves (riser: 8 … 15)
MB_CoilOut [18 … 25]
- riser with disinfection error (riser: 0 … 7)
MB_CoilOut [26 … 33]
- riser with disinfection error (riser 8 … 15)
MB_CoilOut [34 … 41]
- riser with finished disinfection, success (riser: 0 … 7)
MB_CoilOut [42 … 49]
- riser with finished disinfection, success (riser: 8 … 15)
MB_CoilOut [50 … 57]
- riser in disinfection group (riser: 0 … 7)
MB_CoilOut [58 … 65]
- riser in disinfection group (riser: 8 … 15)
MB_CoilOut [66]
- alarm
MB_CoilOut [67]
- disinfection in progress when TS0 is achieved
MB_CoilOut [68]
- permission to run next CCR
MB_CoilOut [69]
- status of binary input : B1
MB_CoilOut [70]
- status of binary input : B2
Data type Register [integer]
Register No.
Description
MB_RegisterOut [0 … 8]
- temperature sensors S0 … S8 (8000 <=> 80 °C)
MB_RegisterOut [9 … 16]
- temperature sensors S9 … S16 (8000 <=> 80 °C)
MB_RegisterOut [17 … 24] - time needed to finished disinfection for risers 1 … 8 [in minutes ]
MB_RegisterOut [25 … 32] - time needed to finished disinfection for risers 9 … 16 [in minutes]
MB_RegisterOut [33]
- selected disinfection time
MB_RegisterOut [34]
- degree of disinfection progress when system is divide for group
MB_RegisterOut [35]
- number of risers in group
MB_RegisterOut [36+0 … 7] - control signal (opening) in % for valve in risers : 1 … 8
MB_RegisterOut [44+0 … 7] - control signal (opening) % for valve in riser: 9 … 16
Baud rate:
data bits
stop bits
parity
9.600
8+1
N
19.200
8+1
N
38.400
8+1
N