Controls of Cascade system

Control of cascade systems can be divided into:
• Condenser capacity control
• Compressor capacity control
• Cascade injection control
• MT evaporator CO2 flow control
• LT evaporator injection control

Condenser capacity control

Capacity control of the condenser can be ac-
complished via step regulation or speed control 
of the fans. 
As regulating sensor for the capacity distribu-
tor the condenser pressure should be selected. 
The reference for the regulation can be defined 
in two ways. Either as a fixed reference or as a 
reference that varies according to the outdoor 
temperature. The reference for the condensing 
pressure is set in °C (°F).

Compressor capacity 
controls

Pack controller AK-PC 740 (up to 4 compressors) 
or AK-PC 780 (up to 8 compressors) controls the 
LT suction pressure and is a standard controller 
for controlling one suction group in any refrigera-
tion system.  The controller is capable of regulat-
ing variable speed of two compressors combined 
with one-step compressors of the same or differ-
ent sizes, depending on the choice of coupling 
pattern.

A unique feature in the AK-PC 740/780 make it 
possible to use the Pc pressure in the LT CO2 side 

as control sensor for the HT suction pressure. This 
to ensure fast and stable control of the condens-
ing pressure of LT CO2 side. 

Low-pressure /
high-pressure coordination

The AK-PC 740/780 is also able to coordinate the 
LT and HT start to ensure a smooth operation.
Here the high-pressure compressors can start 
either as a result of:
- Load on the high-pressure circuit 
- Requirements from the low-pressure circuit 
 
The high-pressure circuit will still ensure that the 
low-pressure circuit is only permitted to start 
when at least one high-pressure compressor has 
started. It will also ensure that security timers and 
compressor timers are complied with.

Oil Management / 
Oil equalisation

The build in oil management system covers most 
systems found on the market to day. Can be used 
with CO2 as well as all other conventional refrig-

erants and support input signals from :
• Level switch on compressor
• Level switch on oil separator
• Level switch on oil receiver
• Pressure transmitter on oil receiver

Oil supply to the compressors is managed by 
activating solenoid valves with user defined ON/
Off pulse sequences. 

HT comp. release
output

LT comp. release.
input

HT comp. request
input

LT comp. request
output

Here both a relay output and an On/off input are used on both control-
lers.

C

ap

. r

eqquest

C

ap

.release

Содержание Cascade HFC

Страница 1: ...R AKS 32R GD DGS AKS 11 AKS 2050 AKS 11 AK PC 740 780 GD DGS AKS 11 AKS 32R AKD 102 AKS 11 DCR Pump SGN AKS 2050 AKS 11 EKC 313 EVR ETS DCR AKD 102 AKD 102 AK CC 450 AKS 11 AKVH AK CC 550 A AKS 11 AK...

Страница 2: ...scharge pressure setting 30 bar 5 C The higher the efficiency of the cascade heat exchanger the lower the difference between the condensation temperature of CO2 and the evaporating temperature of the...

Страница 3: ...d with refrigerant and started up When this is done the CO2 can be filled into the low temperature system The high temperature expansion valve ETS to the cascade heat exchanger should begin simul tane...

Страница 4: ...2 R AKS 32R GD DGS AKS 11 AKS 2050 AKS 11 AK PC 740 780 GD DGS AKS 11 AKS 32R AKD 102 AKS 11 DCR Pump SGN AKS 2050 AKS 11 EKC 313 EVR ETS DCR AKD 102 AKD 102 AK CC 450 AKS 11 AKVH AK CC 550 A AKS 11 A...

Страница 5: ...n the AK PC 740 780 make it possible to use the Pc pressure in the LT CO2 side as control sensor for the HT suction pressure This to ensure fast and stable control of the condens ing pressure of LT CO...

Страница 6: ...medium temperature display cases or rooms is controlled by opening closing a solenoid valve motor valve in the CO2 supply to the evaporator The actual temperature control can take place in two ways as...

Страница 7: ...n evaporator perform ance Stepper motor driver for ETS or CCM expansion valve 0 10 V output for ICMTS valves Electrically operated expansion valves for precise liquid injection in evaporators Fully ba...

Страница 8: ...Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessar...

Отзывы: